-83-
• Alarm reset
Always reset an alarm after ensuring safety by removing the cause of the alarm and turning the
operation signal OFF.
• Alarm release
Always release an alarm after ensuring safety by removing the cause of the alarm and turning the
operation signal OFF.
• Alarm release method
- After the operation swich is set to “STAND-BY”, it can be released by pressing the “S” button.
- Turn off the power, wait for at least 1 minute, and then cycle the power.
• If the product dose not operate properly after the power is cycled, the
internal circuit may be damaged. Contact your nearest sale office.
• Continuing the operation without removing the cause of the alarm may cause
malfunction of the equipment.
• Reset using the ALARM-RESET input
Turn the operation signal OFF and then turn ALARM-RESET input ON (Keep it ON for 10 msec or
more). The ALARM-RESET input is disabled while the operation signal is being ON. The figure
showns an example for which the operation signal is the FWD input.
• Alarm records
Up to 10 generate alarms to save in NVM (Non-volatile memory) in order of the latest to oldest.
When clearing the alarm records, perfrom the alarm record clear on the monitor mode.