BLUEHELIX MAXIMA
209EN
cod. 3541U630 - Rev. 00 - 07/2020
Transparent Parameters “P” menu
A
By selecting a parameter on the screen, the possible values will be shown. If the values shown do not match
those indicated in the corresponding "Range" column, check that the parameter B01 is correctly set to RRT.
Code Description Range Default
P30 Heating ramp 1 ÷ 20°C/minute 4°C/minute
P31
Virtual set point min. tempe-
rature
0= Deactivated
1 ÷ 80°C
0
P32 Heating standby time 0 ÷ 10 minutes 4
P33 Heating Post-Circulation 0 ÷ 255 minutes 15
P34 Pump operation
Fixed flow rate on call
Fixed continuous flow rate
Adaptive flow rate on call
Adaptive continuous flow rate
Adaptive flow rate on call
P35
Modulating pump min.
speed
30 ÷ 100% 30%
P36
Modulating pump start
speed
90 ÷ 100% 90%
P37
Modulating pump max.
speed
90 ÷ 100% 100%
P38
Pump deactivation tempera-
ture during Post-Circulation
0 ÷ 100°C 55°C
P39
Pump activation hysteresis
temperature during Post-
Circulation
0 ÷ 100°C 25°C
P40 Heating user max. setpoint 20 ÷ 90°C 80°C
P41 Max. output in heating 0 ÷ 100% 80%
P42 Burner shutdown in DHW
Fixed
Linked to setpoint
Solar
Fixed
P43
Comfort mode activation
temperature
0 ÷ 80°C 40°C
P44
Comfort mode deactivation
hysteresis
0 ÷ 20°C 20°C
P45 DHW standby time 30 ÷ 255 seconds 120
P46 DHW user max. setpoint 40 ÷ 70°C 55°C
P47 DHW pump Post-Circulation 0 ÷ 255 seconds 30
P48 Max. output in DHW 0 ÷ 100%
BLUEHELIX MAXIMA 24C = 86%
BLUEHELIX MAXIMA 28C = 100%
BLUEHELIX MAXIMA 34C = 100%
P49 Not implemented -- --
P50 Not implemented -- --
P51 Solar off temperature 0 ÷ 100°C 10°C
P52 Solar on temperature 0 ÷ 100°C 10°C
P53 Solar standby time 0 ÷ 255 seconds 10
P54
Heating deltaT adjustment
temperature
0 ÷ 60°C 18°C
P55
Primary exchanger protec-
tion temperature
0 ÷ 150°C 43°C
P56 System min. pressure value 0 ÷ 8bar/10 4 bar/10
P57
System nominal pressure
value
5 ÷ 20bar/10 7 bar/10
P58
Exchanger protection inter-
vention (b01=3)
0
= No F43
1 ÷ 15 = 1 ÷ 15°C/second
10°C/second
P59
Heating hysteresis after
ignition
6 ÷ 30°C 10°C
P60
Timer for heating hysteresis
after ignition
60 ÷ 180 seconds 60
P61
Pump deactivation with
OpenTherm
0 ÷ 1 0