INTRODUCTION
5
Model 12000 18000 24000 30000 30000-3 36000 36000-3 48000-3 UM
Power supply 230-1-50 400-3-50 230-1-50 400-3-50 V-F-Hz
Cooling Capacity
(1)(4)
3500 5300 7000 9000 9000 11600 11600 13500 W
Total power input in cooling mode
(1)(4)
1160 1750 2320 2850 2900 3850 3850 4750 W
Rated current in cooling mode
(1)(4)
5,3 8,1 10,9 13,0 5,3 18,3 6,5 7,9 A
Dehumidification 1,1 1,6 2,3 2,8 2,8 3,8 3,8 5,9 l/h
Heating capacity
(3)(4)
3850 5900 7800 9600 9600 12500 12500 15500 W
Total power input in heating mode
(3)(4)
1200 1830 2300 2800 2800 3750 3750 5050 W
Rated current in heating mode
(3)(4)
5,4 8,6 11,0 12,8 5,2 18,0 6,2 8,2 A
Efficiency class According COOL
to directive 2002/31/CE HEAT
\
Refrigerant R410A Type
Static pressure available 40 50 50 50 50 70 70 70 Pa
Indoor unit air flow rate 580 950 1200 1200 1200 2100 2100 2200 m
3
/h
Sound pressure level Indoor unit
(2)
(max) 48 40 50 50 50 50 50 52 dB(A)
Sound power level Indoor unit 56 48 58 58 58 58 58 60 dB(A)
H
Packging Dimensions I.U. L
P
860 1310 1310 1310 1310 1600 1600 1600 mm
250 310 310 310 310 360 360 360 mm
710 640 640 640 640 880 880 880 mm
Indoor unit net weight 21 36 38 38 58 58 58 58 kg
Outdoor unit air flow rate 2200 3100 3100 3800 3800 4800 4800 5900 m3/h
Sound pressure level Outdoor unit
(2)
54 56 57 59 59 61 61 62 dB(A)
Sound power level Outdoor unit 62 64 65 67 67 69 69 70 dB(A)
H
Packging Dimensions O.U. L
P
875 1027 1027 1050 1050 1105 1105 1045 mm
650 790 790 1000 1000 1100 1100 1380 mm
390 435 435 450 450 420 420 455 mm
Outdoor unit net weight 36 53 56 81 85 93 93 105 kg
Liquid connections Diameter 1/4" 1/4" 3/8" 3/8" 3/8" 1/2" 1/2" 1/2" inch
Gas connections Diameter 1/2" 1/2" 5/8" 5/8" 5/8" 3/4" 3/4" 3/4" inch
TECHNICAL CHARACTERISTICS
Heat pump versions with R410A
(1) Outdoor air temp = 35 °C B.S. - Room temp. = 27 °C B.S. / 19 °C B.U.
(2) Acoustic pressure measured at 1 meter: O.U. in free field, I.U. in 100 m
3
room with reverb. time of 0.5 seconds.
(3) Outdoor air temp. = 7 °C B.S. - Room air temp. = 20 °C B.S.
(4) Running in cooling mode and heating mode at rated conditions, according to EN-14511.
B
ABCDEFG
B
ABCDEFG
B
ABCDEFG
B
ABCDEFG
B
ABCDEFG
B
ABCDEFG
B
ABCDEFG
C