TECHNICAL DATA - BASE VERSION (VB)
NOMINAL performances - Base setting up (AB) - Standard plants
NOMINAL performances - Base setting up (AB) - Standard plants - Data certified by EUROVENT
Data declared according to EN 14511. The values are referred to units without options and accessories.
IR
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 47,2 55,9 63,1 70,5 83,4 94,9 106 120 133 153 173 197
kW
Power input
14,9 17,2 19,8 22,1 27,2 31,2 34,6 38,6 42,7 50,0 55,5 64,6
kW
EER 3,17 3,25 3,19 3,19 3,07 3,04 3,06 3,11 3,11 3,06 3,12 3,05
-
Water flow rate plant side 2,26 2,69 3,03 3,39 4,00 4,56 5,11 5,78 6,40 7,36 8,31 9,46
l/h
Pressure drops plant side 24 34 33 41 31 32 34 33 35 35 38 39
kPa
IP
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 45,3 53,6 60,7 67,8 81,3 92,4 103 115 128 147 166 191
kW
Power input
14,6 17,1 19,4 21,7 26,7 30,2 33,8 37,8 41,8 48,5 54,3 62,8
kW
EER 3,10 3,13 3,13 3,12 3,04 3,06 3,05 3,04 3,06 3,03 3,06 3,04
-
Water flow rate plant side 2,17 2,58 2,91 3,26 3,90 4,43 4,97 5,54 6,16 7,07 7,98 9,17
l/h
Pressure drops plant side 22 31 30 38 29 30 32 30 32 32 35 37
kPa
Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 49,4 58,3 66,0 74,1 88,4 100 113 126 141 161 181 207
kW
Power input
15,5 18,1 20,8 23,4 27,9 31,6 35,5 39,7 44,3 51,0 57,1 65,6
kW
COP 3,19 3,22 3,17 3,17 3,17 3,16 3,18 3,17 3,18 3,16 3,17 3,16
-
Water flow rate plant side 2,35 2,77 3,13 3,52 4,20 4,77 5,35 5,97 6,69 7,64 8,60 9,84
l/h
Pressure drops plant side 26 36 35 44 34 35 37 35 38 38 41 42
kPa
Heating A2W45 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 42,2 49,9 56,4 63,4 75,6 85,8 96,3 108 120 138 155 177
kW
Power input
15,4 17,9 20,5 23,1 27,6 31,2 35,1 39,2 43,8 50,4 56,4 64,8
kW
COP 2,74 2,79 2,75 2,74 2,74 2,75 2,74 2,76 2,74 2,74 2,75 2,73
-
Water flow rate plant side 2,23 2,63 2,98 3,34 3,99 4,53 5,08 5,68 6,35 7,26 8,17 9,35
l/h
Pressure drops plant side 23 33 32 40 31 32 34 32 34 34 37 38
kPa
IR
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 47,4 56,2 63,4 71,0 83,8 95,4 107 121 134 154 174 198
kW
EER 3,22 3,33 3,25 3,29 3,13 3,11 3,15 3,18 3,19 3,14 3,20 3,12
-
Water flow rate plant side 24 34 33 41 31 32 34 33 35 35 38 39
kPa
ESEER 4,58 4,72 4,62 4,67 4,44 4,54 4,47 4,65 4,53 4,58 4,54 4,43
-
IP
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 45,5 53,9 61,0 68,2 81,7 92,8 104 116 129 148 167 192
kW
EER 3,16 3,21 3,19 3,20 3,11 3,11 3,12 3,12 3,14 3,10 3,13 3,11
-
Water flow rate plant side 22 31 30 38 29 30 32 30 32 32 35 37
kPa
ESEER 4,49 4,56 4,54 4,55 4,41 4,55 4,43 4,55 4,46 4,53 4,44 4,42
-
Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 49,2 58,0 65,6 73,6 87,9 99,8 112 125 140 160 180 206
kW
COP 3,22 3,26 3,22 3,21 3,21 3,22 3,22 3,21 3,22 3,20 3,22 3,21
-
Water flow rate plant side 26 36 35 44 34 35 37 35 38 38 41 42
kPa
Frame 1 2 3 4
Model 40.2 50.2 60.2 70.2 80.2 90.2 100.2 115.2 130.2 145.2 160.2 180.2
U.M.
Power supply
400 - 3+N - 50 400 - 3 - 50
V-ph-Hz
Frame 1 2 3 4
Model 40.2 50.2 60.2 70.2 80.2 90.2 100.2 115.2 130.2 145.2 160.2 180.2
U.M.
Power supply
400 - 3+N - 50 400 - 3 - 50
V-ph-Hz