GENERAL FEATURES
IP 40.2 VB AB 0M5
Unit type
IR - Unit suitable for hydronic plant
installation operating as chiller
IP - Unit suitable for hydronic plant
installation operating as reversible heat
pump
BR - Unit suitable for hydronic plant in-
stallation with brine solutions operating
as chiller
BP - Unit suitable for hydronic plant in-
stallation with brine solutions operating
as reversible heat pump
Power supply
5 - 400 V - 3 - 50 Hz
Operating range
M - Medium temperature.
The unit is suitable to be instal-
led in temperate climates.
A - Medium temperature.
The unit is suitable to be instal-
led in tropical climates.
Refrigerant type
0 - R410A
Acoustic setting up
AB - Base setting up
AS - Low noise setting up
AX - Extra low noise setting up
Unit version
VB - Base version
VD - Desuperheaters version
VR - Total recovery version
N° compressors
Unit model
The available special versions are described below:
VB: Standard unit.
VD: Version with Desuperheater (available forboth IR units and IP units)
Produces cold water in the same way as the standard version plus hot water from 30 to 70°C at the same time. This is achieved
by installing a water-refrigerant gas heat exchanger between the compressor and coils in order to recover 25 to 30% of the heating
capacity that would otherwise be dispersed in the air. It helps to remind that hot water production is possible only in combination with
cold-hot water production in the main heat exchanger and it is subordinated by it.
VR: Total Heat Recovery version
Produces cold water as in the standard version plus hot water at a temperature of 30 to 55°C at the same time. This is achieved
thanks to a water-refrigerant gas heat exchanger that totally recovers the heating capacity that would otherwise be dispersed in the
air. The total heat recovery function is enabled and disabled by means of a valve on the compressor delivery of each circuit: when
the temperature of the water that enters the recuperator drops, the valve switches the hot gas flow from the condensing coils to the
recovery heat exchanger. On the other hand, when the temperature of the water reaches the set-point, the valve shuts off the heat
recuperator and switches the hot gas flow to the condensing coils. It helps to remind that hot water production is possible only in
combination with cold water production in the main heat exchanger and it is subordinated by it.
Unit identification code
The codes that identify the units and the meaning of the letters used are described below.
RGA HERGA HE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ferroli RGA HE series and is the answer not in the manual?

Ferroli RGA HE series Specifications

General IconGeneral
BrandFerroli
ModelRGA HE series
CategoryChiller
LanguageEnglish

Related product manuals