37
NOISE LEVELS
The noise levels refer to units operating in the nominal conditions (water temperature: inlet: 12°C - outlet: 7°C, Outdoor air tempera-
ture: inlet: 30°C - outlet: 35°C).
The acoustic pressure levels are measured 1/ 5 / 10 meters away from the outer surface of the unit operating in the free field and
resting on a reflecting surface (directional factor of 2).
Standard Unit AB
MOD.
SWL (dB)
SPL [dB(A)]
Octave bands (Hz) Total
63 125 250 500 1000 2000 4000 8000 dB dB(A)(E) 1 m 5 m 10 m
350.5
99.2 95.5 95.4 93.0 90.2 85.5 80.1 72.0 103 95 75 67 63
390.6 99.2 95.5 95.4 93.0 90.2 85.5 80.1 72.0 103 95 75 67 63
440.6 100.4 98.2 95.8 93.4 90.9 87.9 80.1 70.6 104 96 76 68 64
490.6 100.4 98.2 95.8 93.4 90.9 87.9 80.1 70.6 104 96 76 68 64
560.6 101.4 99.2 96.8 94.4 91.9 88.9 81.1 71.6 105 97 77 69 65
630.6 101.4 99.2 96.8 94.4 91.9 88.9 81.1 71.6 105 97 77 69 65
Low noise unit AS
MOD.
SWL (dB)
SPL [dB(A)]
Octave bands (Hz) Total
63 125 250 500 1000 2000 4000 8000 dB dB(A)(E) 1 m 5 m 10 m
350.5
95.4 93.0 90.8 86.3 83.4 79.8 71.3 62.0 99 89 69 61 57
390.6 95.4 93.0 90.8 86.3 83.4 79.8 71.3 62.0 99 89 69 61 57
440.6 95.1 91.2 90.3 88.2 85.1 80.0 73.4 65.9 98 90 70 62 58
490.6 95.1 91.2 90.3 88.2 85.1 80.0 73.4 65.9 98 90 70 62 58
560.6 96.1 92.2 91.3 89.2 86.1 81.0 74.4 66.9 99 91 71 63 59
630.6 96.1 92.2 91.3 89.2 86.1 81.0 74.4 66.9 99 91 71 63 59
Extra low moise unit AX
MOD.
SWL (dB)
SPL [dB(A)]
Octave bands (Hz) Total
63 125 250 500 1000 2000 4000 8000 dB dB(A)(E) 1 m 5 m 10 m
350.5
92.4 90.0 87.8 83.3 80.4 76.8 68.3 59.0 96 86 66 58 54
390.6 92.4 90.0 87.8 83.3 80.4 76.8 68.3 59.0 96 86 66 58 54
440.6 94.2 91.9 89.4 85.3 81.0 74.6 67.0 58.6 97 87 67 59 55
490.6 94.2 91.9 89.4 85.3 81.0 74.6 67.0 58.6 97 87 67 59 55
560.6 92.4 90.1 88.6 86.0 83.3 77.8 71.2 62.8 96 88 68 60 56
630.6 92.4 90.1 88.6 86.0 83.3 77.8 71.2 62.8 96 88 68 60 56
(E): Data declared according to EUROVENT LCP certification programme. The values are for units without options and accessories.
Open field
Q=2
SWL = Sound power levels, with reference to 1x10
-12
W.
The Total sound power level in dB(A) measured in compliance
with ISO 9614 standards, is certified according to the Eurovent
certification program and it is the only mandatory value (the va-
lues of octave band in the table are indicative).
Eurovent certification (E) exclusively refers to the Total Sound
Power in db(A), which is therefore the only binding acoustic spe-
cification (the values of the Octave bands in the table are indi-
cative).
SPL = Sound pressure levels, with reference to 2x10
-5
Pa.
The sound pressure levels are values calculated by applying the
ISO-3744 relation (Eurovent 8/1) and refer to a distance of 1
meter away from the external surface of units operating in the
open field with directivity factor 2 (Q=2) and the units operating
in nominal conditions in the cooling mode.