What to do if the shunt field current is too low on a Fincor Controller?
- MMisty WheelerSep 14, 2025
If the shunt field current is too low: * Check the motor shunt field and associated circuitry for a loose connection or a broken wire. Repair accordingly. * Check the motor rating, as the shunt field may be connected for incorrect voltage. * Replace BR1 or the control board, as there may be a Shunt Field Bridge BR1 failure.