Document #51003 Rev.E 01/11/02 P/N 51003:E
9
Product Description
CHAPTER 1 Product Description
The Fire•Lite MS-9200(C) is a compact, cost effective, addressable FACP (Fire Alarm Control Panel) with an exten-
sive list of powerful features. The combination of Fire•Lite's newer series devices and legacy 300 Series Addressable
Devices, along with the MS-9200 FACP offers the latest in fire protection technology. The power supply and all elec-
tronics are contained on a single circuit board housed in an attractive metal cabinet, providing a complete fire control
system for most applications. Optional modules, which plug into the main circuit board, are available for special
functions. Available accessories include LED, graphic and LCD annunciators, digital communicator, local down-
loading software and remote power expansion. The MS-9200E offers the same features as the MS-9200(C) but
allows connection to 220/240 VAC input.
Note: Unless otherwise specified, the term MS-9200 is used in this manual to refer to both the MS-9200(C) and the
MS-9200E FACPs (Fire Alarm Control Panels).
1.1 Features
Single standard SLC loop which meets NFPA Style 4, 6 and 7 requirements
198 addressable device capacity (99 detectors and 99 monitor/control modules)
56 software zones
Two main circuit board NACs (Notification [bell] Appliance Circuits) expandable via control modules
Optional RTM-8F eight zone relay module with local energy/reverse polarity transmitter
Optional ACM-8RF Relay Control Module
Printer/PC Interface
3.6 amps system power expandable to 6.6 amps
3.0 amps NAC power expandable to 6.0 amps
40 character LCD display (backlit)
Real-time clock/calendar
History file with 500 event capacity
Advanced fire technology features:
Automatic device type-code verification
Addressable smoke detector data printout
Auto detector test
Maintenance alert
Point trouble identification
Waterflow (nonsilenceable) selection per module point
Supervisory (latching or auto-resettable) selection per point with separate system LED. Note that the
auto-resettable feature is only available for panels with software version #M9200V20 or later.
System alarm verification selection
Walktest with report of two devices set to same address
Presignal per NFPA 72
Annunciators
ACS LED Zone Annunciator Series
LDM Graphic Annunciator Series
LCD-40 Series Liquid Crystal Point Display Annunciator
Silence inhibit timer option
Autosilence timer option
Continuous/March Time/Temporal or California code for main circuit board NACs

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fire-Lite MS-9200(C) and is the answer not in the manual?

Fire-Lite MS-9200(C) Specifications

General IconGeneral
BrandFire-Lite
ModelMS-9200(C)
CategoryControl Panel
LanguageEnglish

Related product manuals