Master Programming Level Programming
MS-9200UD PN 51906:A 12/10/02 111
4+2 Standard, 4+2 Express, 3 + 1, 4 + 1 and 4+2 Expanded Formats
The information shown in Table 3.3 is automatically programmed for the Central
Station phone number Event Codes when any of these Formats are selected. Enter
00 for an Event Code Setting to disable the report.
Table 3.3 Event Codes
Event Description Event Code Settings
Active Restoral
PULL STATION 11 E1
MON-USER-DEF-1 11 E1
WATERFLOW 11 E1
MON-USER-DEF-2 11 E1
SMOKE (PHOTO) 11 E1
DET-USER-DEF-1 11 E1
SMOKE (ION) 11 E1
DET-USER-DEF-2 11 E1
HEAT DETECT 11 E1
DET-USER-DEF-3 11 E1
SMOKE DUCT-P 11 E1
DET-USER-DEF-4 11 E1
DUCT SUPERVISORY 81 E1
DET-USER-DEF-5 81 E1
not used 00 00
not used 00 00
not used 00 00
not used 00 00
MONITOR 11 E1
MON-USER-DEF-3 11 E1
not used 00 00
not used 00 00
SMOKE CONVEN 11 E1
MON-USER-DEF-5 11 E1
HEAT DETECT 11 E1
MON-USER-DEF-6 11 E1
MEDIC ALERT 00 00
MON-USER-DEF-7 00 00
HAZARD ALERT 00 00
MON-USER-DEF-8 00 00
TORNADO ALRT 00 00
MON-USER-DEF-9 00 00
not used 00 00
not used 00 00
TAMPER 81 E1
MON-USER-DEF-11 81 E1
MON SUPERVISORY 81 E1
MON-USER-DEF-12 81 E1
MON SUPERV AUTO 81 E1
MON-USER-DEF-13 81 E1
POWER MON 81 E1
MON-USER-DEF-14 81 E1
TROUBLE MON 81 E1
MON-USER-DEF-15 81 E1
PROCESS MON 00 00