FireClass Panels and Repeaters Loops installation
Installation Guide Doc. version 2.0 14
6 Loops installation
As detailed below, the procedure is to install the loops
into the building, making temporary wiring arrange-
ments for testing. Then, once testing has been com-
pleted, the final loop connections can be made.
6.1 Running and temporarily
connecting the loops
1 Run the loop wiring around the building, and wire in
the bases, according to the system plan. Similarly,
run any other wiring required for ancillary modules.
Clearly label the loop conductors as being positive or
negative.
At this stage, do not wire in any isolator bases, or
other modules, or fit the detectors. This is to avoid
potential damage caused by the high voltage insula-
tion checks. Use strip connectors (Fig. 11) for any
temporary connections, to preserve continuity.
For connection details see the individual leaflets or
labels provided with the products.
2 At the control panel, feed the loop cables through
the appropriate knockouts. Use suitable cable glands
as needed. To maintain IP30 pass test status, use a