23 Installation Guide Doc. version 2.0
Local FC-FI/FC-FI-1board connections FireClass Panels and Repeaters
11.1 Local FC-FI/FC-FI-1board
connections
11.2 Connecting local sounders
Local sounders are sounders connected directly to the
FC-FI/FC-FI-1 board, as opposed to sounders on the
addressable loop.
Connect the sounders as shown in Fig. 18 (Item 4). The
figure only shows one sounder, but multiple sounders
can be connected in parallel.
The terminating capacitors are included in the shipment.
Fit the capacitors beyond the furthest sounder. The
capacitors can be connected with either polarity. If a
control panel sounder output is not required, connect
the capacitor directly across the sounder output termi-
nals.
NOTICE
There is a danger of signal interference
between cable runs.
Take care when laying out transmission
lines to avoid the potential for cross-
coupling between them.
Fig. 17: FC-FI-1 - Field Interface Board. The FC-FI-1 is used in the FC602S and the FC602S Scandinavian panels.