FireClass Panels and Repeaters Mounting a FB800 15WAY fuse board on a FC600 series panel
Installation Guide Doc. version 2.0 36
14 Mounting a FB800
15WAY fuse board
on a FC600 series
panel
1 Unplug any cards or boards that are already fitted.
2 Note the positions of the cables connected to the
cards or boards.
3 Refer to section 12.3 Mounting cards and boards on
a FC600 series Lite panel and Fig. 22. Mounting the
FB800 board requires the use of an old cards adapter
bracket (120.008.130) from the optional P-EXP Panel
Expansion Kit (557.202.807), item 5 in Fig. 22.
4 Attach the old cards adapter to the existing cards
using pillars (items 3 in Fig. 22). Secure with M3 x
6mm screws (items 6 in Fig. 22).
5 Mount the FB800 board on to the old cards adapter
using M3 x 6mm screws and washers.
6 Connect all necessary cables to the FB800 board.
14.1 FB800 15WAY fused 24V outputs board details
DANGER
Make sure that the replacement fuse is of
the correct current rating. Failure to
insert the correct fuse can lead to injuries
and damage to the equipment.
If fuse FU2 needs replacing, send the
board for repair.
Note
Before you undertake this procedure, power
down the panel by isolating the mains and
removing the battery fuse.
Fig. 24: FB800 terminal positions
XT1 XT2
XT3
FU15
FU14
FU13
FU12
FU11
FU10
FU9
FU8
FU7
FU6
FU5
FU4
FU3
FU2
FU1
;3
12
;3
1
2
Out 1 Out 2 Out 3 Out 4 Out 5
+- + - + - + - + -
+ - + - + - + - + -
Out 6 Out 7 Out 8 Out 9 Out 10
+ - + - + - + - + -
Out 11 Out 12Out 13 Out 14 Out 15
Connector Function
XT1 Power 24V fused Outputs 1 to 5
XT2 Power 24V fused Outputs 6 to 10
XT3 Power 24V fused Outputs 11 to 15
XP4 Power 24V Input
Table 30: FB800 Terminal Functions
XP5 Power 24V Output
Connector Function
Table 30: FB800 Terminal Functions