FireClass Panels and Repeaters Jumper and DIP switch settings
Installation Guide Doc. version 2.0 28
Table 6: RBUS switches on FC-FI
Device SW6: A
XP4 1A
SW6: B
XP4 1B
SW6: C
XP4 2A
SW6: D
XP4 2B
SW6: E
XP4 3A
SW6: F
XP4 3B
CUI ON ON ON ON OFF OFF
Black Box OFF OFF ON ON OFF OFF
Fig. 21:RBUS communications link between the FC-FI and the standard CUI and repeater CUI
Jumper 1-2 2-3 OPEN
J1 – Relay 3
Normally Closed
[1]
Normally Open N/A
J2 – Relay 4
Normally Closed
[1]
Normally Open N/A
J3 – MCPU Watchdog
Enabled
[1]
Active (MCPU in reset) Enabled
J4 – LIOMCU Watchdog
Enabled
[4]
Active (LIOMCU in reset) Disabled
J5 – MCPU Boot Mode
[2]
H1 Header
H2 Header
H3 Header
LIOMCU Boot Mode
[3]
Enabled
Enabled
Enabled
Enabled
Enabled
-
-
-
-
-
Disabled
[1]
Disabled
[1]
Disabled
[1]
Disabled
[1]
Disabled
[1]
Table 7: FC-FI/FC-FI-1 - jumper settings
[1] Default.
[2] For updating the MCPU Boot Loader. The mode is entered after an MCPU reset.
[3] For updating the LIOMCU firmware. The mode is entered after a LIOMCU rest. The LIOMCU Watchdog has to be disabled
during update of firmware.
[4] Default. Disable this before a firmware update.