EasyManua.ls Logo

FireClass J400REP - INSTALLING THE CONTROL PANEL; Installing Accessory Modules

Default Icon
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLING THE CONTROL PANEL
!
Installation of this system must be carried out
strictly in accordance with the instructions in
this section, and in compliance with the local
safety regulations in force.
Ø
Choose suitable mounting locations for the Control
panel, detectors, fire warning and fire control devices.
Ø
Lay the cables between the Control panel and the
system peripherals.
Ø
If necessary, install any accessory modules (Expan
-
ders, etc.).
Ø
Mount the Control panel to the wall.
Ø
Carry out the necessary connections, leaving the po
-
wer-supply connection until last.
Ø
Program the Control panel in accordance with the in
-
structions in the “PROGRAMMING” section.
Ø
Test the entire system (Control panel, detectors, fire
warning and fire control devices).
+
Accessory Modules (Expanders Modules, Extin-
guishment Modules, etc.) should be installed befo-
re mounting the Control panel to the wall.
Installing accessory boards
!
Ensure that the Control panel power supply
(Mains and Batteries) has been disconnected
before installing any accessory the Modules.
+
Accessory Modules must be enrolled.
n
Installing Extinguishment Modules
J408 The J408 can house 1 Extinguishment Module, posi
-
tioned as shown on page 14 (see part no. 28). To install the
Extinguishment Module, work through the following steps.
1. Remove the screws 4 and open the Control panel.
2. Hold the unit with the component side facing you.
Insert the Extinguishment Module under the clips 86
on the top part of the housing (see Figure 7a), then
snap it gently into place. Ensure that it is resting
properly on the plastic support pins 87 (see Figu-
re 7a) and that it is held firmly in position by the clips
88 (as per Figure 7b).
3. Ensure that the Jumpers, marked “1” and “2” on the
PCB (43 and 59 in the Parts Description Table”)
are inserted (Extinguishment Module no. 1).
4. Using the Flat cable (27), connect the Extingui
-
shment Module to the Main Board, via the jacks (58
and 63 respectively).
5. Place the label provided with the Extinguishment
Module next to the data label that is already present
on one of the Control panel’s sides.
+
The polarity of the Flat cable connectors must be
observed.
J424 The J424 Control panel can house 2 Extingui
-
shment Modules (28 and 31 in the Figure on page 12).
Install the Extinguishment Module, as follows.
1. Remove the screws (4) and open the Control panel.
2. Fit the spacers (91) onto the plastic pins (90).
3. Using the nuts (93), secure the Extinguishment Mo
-
dule in position.