n
NAC2 Output
Pre-Alarm pattern To be set up in the same way as
the Pre-Alarm pattern of NAC1 but for the Pre-Alarm
pattern of NAC2.
Pre-Alarm Default setting: NAC2 WILL NOT ACTIVATE
during the Pre-Alarm Time.
Alarm pattern To be set up in the same way as the
Alarm pattern of NAC1 but for the Alarm pattern of NAC2.
Default setting: NAC2 is continuous.
Bistable If this option is enabled, the NAC2 Output
returns to standby when all zones have returned to
standby, irrespectively of the Control panels’ status. If
this option is disabled (factory default), the NAC2 Out
-
put returns to standby when the Control panel is reset.
+
If the Bistable option is enabled, this will void com
-
pliance with Standard EN54-2 of the NAC2 Output.
n
ALARM Output
Alarm Pattern To be set up in the same way as NAC1
but for the Alarm pattern of the ALARM Output.
Default setting: the Alarm Output is continuous.
NON-Silenceable If this option is ENABLED, the
ALARM Output cannot be SILENCED.
n OC Output Events
This section will allow you to assign one or more of the
following events to the OC Output ([OC] terminal), as
follows.
Alarm If you assign this event, the OC Output will acti-
vate when the Control panel generates an Alarm, and
will restore to standby when the Control panel Resets.
Pre-Alarm If you assign this event, the OC Output will
activate when the Control panel generates Pre-Alarm,
and will restore to standby when the Control panel ge
-
nerates an Alarm.
Fault If you assign this event, the OC Output will acti
-
vate when the system detects trouble, and will restore
when the trouble clears.
Reset If you assign this event, the OC Output will acti
-
vate when the system generates Reset, and will remain
active until Reset is completed.
Disable If you assign this event, the OC Output will ac
-
tivate when Zones are Disabled, and will restore when
the Zones are Re-Enabled.
Test If you assign this event, the OC Output will acti
-
vate when Zones are in Test status, and will restore
when Test status ends.
Double Knock If you assign this event, the OC Output
will activate when TWO or more Zones generate Alarm,
and will restore to standby when the Control panel Re
-
sets.
+
If you assign more than one event, the OC Output will
activate when one of the assigned events occurs,
and will Reset when ALL the assigned events end.
n
DL Output
The Dialler Output ([DL] terminal) will activate when its
programmed delay expires. The delay countdown will
start when the Control panel generates Alarm status.
+
If the Alarm is triggered from a Call point (connec-
ted to a Zone with the Call point priority option
ENABLED), the DL Output will activate instantly.
Alarm Signalling Delay This field will allow you to pro-
gram the Dialler Output delay.
Accepted values: 0 through 600 seconds (10 minutes),
in steps of 10 seconds;
Default setting: 60 seconds.
+
The Alarm Signalling Delay will be suspended
during the Silence phase.
PROGRAMMING FROM A PC 41
Figure 26 The Outputs page