Man. Preest-Ex. T. (Key/LED 4)
The LED will go On to indicate that the system is ready
to start the programming procedure.
Use the Increase Time option (Key 8)orDecrease
Time option (Key 0), respectively, to increase or decre
-
ase the setting. The setting is achieved by adding toget
-
her the values preceded by and , indicated by the
LEDs in column B (e.g. if the 16 sec and 4 sec LEDs
are On, the setting will be 20 seconds (16+4)).
n
Reset Inhibit T. (Key/LED 5)
The LED will go On to indicate that the system is ready
to start the programming procedure.
Use the Increase Time option (Key 8)orDecrease
Time option (Key 0), respectively, to increase or decre
-
ase the setting. The setting is achieved by adding toget
-
her the values preceded by and , indicated by the
LEDs in column B (e.g. if the 16 sec and 4 sec LEDs
are On, the setting will be 20 seconds (16+4)).
n
Zones (Key/LED 7)
The LED will go On to indicate that the system is ready
to start the programming procedure.
Using the Zone keys (Z1 to Z8for the J408; Z1 to Z24for
the J424) ENABLE/DISABLE the respective Zones for
“Activation” of the Extinguishment Module concerned:
– if the respective Zone LED is On, the Zone will trigger
activation of the Extinguishment Module concerned;
– if the respective Zone LED is Off, the Zone will NOT trig-
ger activation of the Extinguishment Module concerned.
LCD Module
The LCD Module will allow you to program the following
parameters from a J424 Control panel or from a
J400-REP Repeater panel:
Ø LCD Module Address
Ø
Zone Descriptions
Ø
Strings Update
Date Format
To access the programming phase, insert the LCD Mo
-
dule jumper 82, the module will provide the Main menu.
n
Programming Mode Address
Program this option as follows.
1. Using Ú or Ù, select the Programming Mode
Address option:
PROGRAMMING MODE
ADDRESS : 1
2. Using Ø or ×, assign the respective Address to the
LCD Module.
PROGRAMMING MODE
ADDRESS : 4
+
If you are using an LCD Module with a J424, assign
Address 4. If you are using an LCD Module with a
Repeater panel, assign the Repeater panel Address.
n
Zones Descriptions
1. Using Ú or Ù, select Zones Descriptions:
ZONE DESCRIPTION
press ENTER
2. Press Enter:
ZONE 1
Zone 1
3. Using Ø or ×, select the character you want to
change (the selected character will blink).
Using Ú or Ù, select the new character.
ZONE 1
Warehouse
4. Press Enter to save the Description on the screen
and step back or,pressEsc to save the Description
on the screen and go back to the Main Menu.
+
Any changes made to the Descriptions — via the LCD
Module — must be broadcasted to the other Modules
by means of the Strings Update command.
n Strings Update
1. Using Ú or Ù, select Update Strings.
STRINGS UPDATE
press ENTER
2. Press Enter to update the Descriptions.
UPDATE
EXECUTED
3. Press Esc to go back to the Main Menu..
n
Date Format
1. Using Ú or Ù, select Date Format:
DATE FORMAT :
dd/mm/yyyy
2. Using Ø or ×, select the date format:
– dd/mm/yyyy = day/month/year;
– mm/dd/yyyy = month/day/year.
DATE FORMAT :
mm/dd/yyyy
3. Press Enter or Esc to confirm and go back to the
Main menu.
50 Conventional Fire Panels J424/J408