EasyManua.ls Logo

FireClass J400REP - Connecting Call-Points; Connecting Gas Detectors

Default Icon
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Bypass Missing Detectors If this option is enabled,
the zone concerned will exclude any inoperative (Mis
-
sing) detectors from the system configuration, thus allo
-
wing detectors connected downstream of ‘Missing’ de
-
vices to operate as normal.
Wiring instructions for this feature:
Connect 1N5819 diodes (or similar) to the power in
-
put and output terminals of all the detectors but the last,
then connect a 1N5819 diode to the power output ter
-
minal and the negative terminal of the last detector (see
part nr. 110 in Figure 14).
+
The polarity of the diodes must be observed (see
Figure 14: the white band on part nr. 110 indicates
the cathode.
The Control panel monitors the system for “Missing” de
-
vices by inverting the polarity (every 60 seconds) of ter
-
minals belonging to zones with the Bypass Missing
Detectors attribute (option ENABLED).
+
Polarity inversion DOES NOT damage the detec
-
tors as, during this status, only a 0.6 V negative vol
-
tage is present on the detector power terminals .
n
Connecting Call-points
This Control panel accepts Normally Open Call-points
with 680 ohm contact resistance (wiring as per Figu-
re 14), and Call-points with zero ohm contact resistan-
ce (wiring as per Figure 15).
Wiring instructions
Connect a 680 ohm (112) resistor in series to the Nor-
mally-Open contact, then connect the series of the
contact with the resistor and the Normally-Open contact
to the zone terminal.
If the Call point is the last device or the zone, connect
the EOL (109) to its NO and C terminals.
Call-point priority The zone concerned will discrimi
-
nate between alarms triggered by Detectors and those
triggered by Call-points. In the event of a Call-point
alarm, the Control panel will generate an instant alarm
regardless of the operating mode of the system (Day or
Night Mode).
Wiring instructions for this feature:
Use Call-points with 270 ohm contact resistance, or
connect a 270 ohm resistor in series to a Call-points
with zero ohm contact resistance, as shown in Figu
-
re 15 (111).
n
Connecting Gas Detectors
This Control panel accepts Gas detectors with Normally
Open Outputs (NO) and 4-20 mA gas detectors.
NO Output Connect Gas detectors with Normally
Open Outputs (NO) as per Figure 16a.
Operating principles:
Terminal [A] (the Detector Alarm Output) will connect to
terminal [–] when the concentration of gas in the area
exceeds the preset safety threshold.
Wiring description:
Using a 680 ohm resistor (115), connect terminal [A] to
the zone terminal.
Connect terminal [+] (the Detector Power input) to a po
-
wer source that can be interrupted for the required reset
time (see terminal [24R] on the Main Board).
Terminal [P] signals the pre-alarm status of the detec-
tor. If this state is to be detected, terminal [P] must be
connected to the zone (refer to Figure 16a) using an
820 ohm resistor (116) and the zone should be pro-
grammed with the attribute Double N.O. Gas detector,
as described under "Zones" in the “PROGRAMMING
FROM A PC" section.
30 Conventional Fire Panels J424/J408
NO
C
Z3
R3
24R
NO
C
NO
C
Zero ohm
call-point
Main board or
Expander board
Main
board
112
NO output
detector
111 111
NO output
detector
109
Figure 15 Wiring diagram of 3 detectors with Normally-Open Outputs and a Call point with zero ohm contact resistan
-
ce: 109) 3900 ohm, 1/4 W EOL resistor (orange-white-red-gold); 111) 680 ohm resistor;
112) 680 ohm resistor (necessary when Call-point priority option is DISABLED) or 270 ohm resistor when Call-point
Priority option is ENABLED).

Table of Contents

Related product manuals