Configuration 1 (Key/LED 5)
The LED will go On to indicate that the system is ready
to start the programming procedure. Using the keys in
columns E and F, configure the Control panel:
if the LED is On, the respective Module is included in
the configuration;
if the LED is Off, the respective Module is NOT inclu
-
ded in the configuration.
During this phase, the keys and LEDs in columns E and
F will operate in accordance with the options written in
positive type:
Ø
Exting. 1 = Extinguishment Module nr. 1
Ø
Exting. 2 = Extinguishment Module nr. 2
Ø
Expander 1 = Expander Module nr. 1
Ø
Expander 2 = Expander Module nr. 2
Ø
Power 1 = Power Station nr. 1
Ø
Power 2 = Power Station nr. 2
Ø
Power 3 = Power Station nr. 3
Ø
Power 4 = Power Station nr. 4
n
Configuration 2 (Key/LED 7)
The LED will go On to indicate that the system is ready
to start the programming procedure. Using the keys in
columns E and F, configure the Control panel:
if the LED is On, the respective Module is included in
the configuration;
if the LED is Off, the respective Module is NOT inclu-
ded in the configuration.
During this phase, the keys and LEDs in columns E and
F will operate in accordance with the options written in
negative type:
Ø LCD 1 = LCD Module nr. 1
Ø LCD 2 = LCD Module nr. 2
Ø LCD 3 = LCD Module nr. 3
Ø LCD 4 = LCD Module nr. 4
Ø Rep. 1 = Repeater panel nr. 1
Ø
Rep. 2 = Repeater panel nr. 2
Ø
Rep. 3 = Repeater panel nr. 3
Ø
Rep. 4 = Repeater panel nr. 4
The “MODULES” Programming Phase
+
The Activation Mode may ONLY be programmed
THROUGH A PC.
The MODULES LED will blink to indicate that the system is
ready to program the parameters of the Extinguishment
Modules. During this phase, the keys and LEDs will opera
-
te in accordance with the options preceded by in the pa
-
nes on the Programming Overlay, see Figure 35.
The LED (Exting. 1 or Exting. 2) corresponding to the
Extinguishment Module concerned will blink to indicate that
the system is ready to program the respective parameters.
Press key 1 (Extinguish. Time), 2 (Pre-Exting. Time),
4 (Man. pre-Ext. T.), 5 (Reset Inhibit T.)or7 (Zones)
to select the parameter to be programmed, then read
the relevant sub-section, or press key 9 (Next Phase)
to go back to the ZONE Programming.
n
Extinguish. time (Key/LED 1)
The LED will go On to indicate that the system is ready
to start the programming procedure.
Use the Increase Time option (Key 8)orDecrease
Time option (Key 0), respectively, to increase or decre
-
ase the setting. The setting is achieved by adding toget
-
her the values preceded by and , indicated by the
LEDs in column B (e.g. if the 20 sec and 40 sec LEDs
are On, the setting will be 60 seconds (20+40)).
n Pre-exting. time (Key/LED 2)
The LED will go On to indicate that the system is ready
to start the programming procedure.
Use the Increase Time option (Key 8)orDecrease
Time option (Key 0), respectively, to increase or decre-
ase the setting. The setting is achieved by adding toget-
her the values preceded by and , indicated by the
LEDs in column B (e.g. if the 16 sec and 4 sec LEDs
are On, the setting will be 20 seconds (16+4)).
PROGRAMMING FROM THE PANEL 49
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
4-20mA gas
5sec
N
1sec
C
10 sec
N
2sec
Test on NACs
20 sec
NAC1 Alarm
4sec
40 sec
NAC2 Alarm
8sec
NON silen. R
80 sec
ALARM
16 sec
160 sec
OC output
32 sec
Alarm verific.
320 sec
64 sec
2 x N.O. gas?
640 sec
128 sec
MODULES
VARIOUS
PANEL
OUTPUTS
TIMES
ZONES
-
Investigation time
Pre-alarm
Day mode
Reset time
Pre-extin
g
. time
Zone 1
Zone 1
Fault
ALARM
Exting. 1 LCD 1
Zone 5
Zone 5
Power 1 Re
p
.1
Zone 5
Zone 2
Zone 2
Test
Exting. 2 LCD 2
Zone 6
Zone 6
Power 2 Re
p
.2
Zone 6
Zone 3
Zone 3
Expander 1 LCD 3
Zone 3
Zone 7
Zone 7
Power 3 Re
p
.3
Zone 7
Zone 4
Zone 4
Expander 2 LCD 4
Zone 4
Zone 8
Zone 8
Power 4 Re
p
.4
Zone 8
Zone 2/Extin
g
.2
-
Verification time
Reset
Ni
g
ht mode
NON silence. outs
Man. pre-ext. t.
-
Pre-alarm time
Alarm
User code
Stabilization time
Extinguish. time
-
Silence time
Disablement
Clock
Configuration 1
Reset Inhibit t.
-
Confi
g
uration 2
DL output delay
Double knock
Date
Zones
-
DL output delay
Double knock
Date
Confi
g
uration 2
Zones
12 3
45 6
78
90
Next Option
Decrease time
Next Output
Decrease time
Decrease time
-
Increase time
Mains OFF delay
Increase time
Increase time
Next phase
CBA E FD
Pre-alarm on R
Detect missing
Call-point alarm
NAC2 Pre-alarm
NAC1 Pre-alarm
Zone 1/Extin
g
.1
R out
bistable
Figure 35 The “Modules” Programming Phase