Panel Settings
The Panel Settings page will allow you to program the
following parameters.
n
Day/Night
Automatic Night to Day Mode If this option is
ENABLED, the changeover from Night Mode to Day
Mode will occur automatically at the set Time (refer
to “Night to Day Mode” in this section).
Automatic Day to Night Mode If this option is
ENABLED, the changeover from Day Mode to Night
Mode will occur automatically at the set Time (refer to
“Day to Night Mode” in this section).
Night to Day Mode This field will allow you to program
when the Control panel must change from Night to Day
Mode.
This setting requires two digits for the Hour value and
two for the Minutes value.
Use 00 to 23 (00 = Midnight) to set the Hour value.
Use 00 to 59 to set the Minutes value.
Day to Night Mode This field will allow you to program
when the Control panel must change from Day to Night
Mode.
This setting requires two digits for the Hour value and
two for the Minutes value.
Use 00 to 23 (00 = Midnight) to set the Hour value.
Use 00 to 59 to set the Minutes value.
n Reset
The Control panel Reset operation is divided into two
phases: Reset and Stabilization.
During the Reset phase, the Control panel will interrupt
the power supply to the devices connected to the Zones
and the [24R] terminal.
During the Stabilization phase, the Control panel will
ignore the status of the Zones.
This process is necessary, as some devices signal trou
-
ble conditions for several seconds after power-up.
The Reset section will allow you to program the Detec
-
tor Reset and Stabilization Times.
Detector Reset Time This field will allow you to pro
-
gram the length of the power interruption that will reset
the Detectors.
Accepted values: 0 through 15 seconds, in steps of 1
second.
Default setting: 8 seconds.
Detector Stabilization Time This field will allow you
to program the length of time (necessary after Reset)
that the system will ignore the Zone Status.
Accepted values: 0 through 5 seconds, in steps of 1 se
-
cond.
Default setting: 2 seconds.
n
User Code
The 4-digit User Code will allow access to Level 2 of the
Control panel.
Default setting: 1234
n
Alarm Verification Time
This field will allow you to program the Alarm verification
window, that is, the time within which a Zone (with the
Alarm Verification option ENABLED) must trigger two
Alarm events in order for the system generate a Control
panel Alarm.
Accepted values: 10 through 600 seconds (10 minu-
tes), in steps of 5 seconds
Default setting: 60 seconds
n Extinguishment Termination Code
The Extinguishment Termination Code is a 4-digit num-
ber that allows the Extinguishment Time to be stopped
for test purposes (refer to “Testing The Extinguishment
Module” in the “INSTALLING THE CONTROL PANEL”
section.