EasyManua.ls Logo

FireClass J400REP - Programming Panel Settings and Modules

Default Icon
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
For step by step instructions on how to set up the Thre
-
sholds:
select the Wizard Thresholds” button.
+
The Wizard Thresholds option can be used only
when the Control panel connected to a computer,
and is in “Programming” status (as described in the
“Downloading” paragraph).
n
Options
This section will allow you to assign the Zone “attributes”.
Alarm Verification If this option is ENABLED, Alarm
will be verified as follows:
Ø
the system will not generate a Control panel Alarm
when the Zone first detects Alarm conditions;
Ø
the system will reset the Zone and start the Alarm
Verification Time (refer to “Panel settings”);
Ø
if the Zone triggers another Alarm while the Alarm
Verification Time is running, the system will generate
a Control panel Alarm.
Bypass missing detectors If the Zone is wired to
bypass missing detectors, this option MUST BE ENABLED.
NON-Silenceable R Output If this option is
ENABLED, the Repeat Output of the Zone concerned
([Rn] terminal) CANNOT be Silenced.
Pre-Alarm on R Output If this option is ENABLED, the
Control panel will activate the Repeat Output of the Zone
concerned ([Rn] terminal) during the Pre-Alarm phase.
Test zone on NACs If this option is ENABLED, the
Control panel will activate the NAC1 and NAC2 Outputs
for 1 second when the Zone is undergoes testing.
Gas Detector If this option is ENABLED, it will be possible
to connect a 4 - 20 mA Gas Detector to the Zone terminal.
+
The Gas Detector option can be ENABLED ONLY
for Zones 1, 9 and 17, respectively, the [Z1] termi
-
nals on the Main Board, and on Expander nr. 1 and
Expander nr. 2.
Double N.O. Gas Detector This option should be
enabled when using terminal [P] of the detector. When
this option is ENABLED, Zone thresholds will be auto
-
matically adjusted to the connection illustrated in Figure
16a on page 31. Thus, the Control panel will be able to
detect 2 activation thresholds, one for the Pre-Alarm
and one for the Alarm.
R Output Bistable This option is only available when
the Double N.O. Gas detector is enabled.
In this case, when the option R Output Bistable is ena
-
bled, the R Output of the zone is activated when the zone
exceeds the alarm threshold (or the pre-alarm threshold,
if the option “Pre-Alarm on R Output” is enabled) and re
-
turns to standby when the zone falls below the alarm
threshold, irrespectively of the Control panel status.
If the option R Output Bistable is disabled (factory de
-
fault), the R Output returns to standby when the Control
panel is reset.
n
Times
Pre-Alarm Time This field will allow you to program the
delay between the Zone Alarm and the Control panel Alarm.
+
If several Zones trigger Alarms within seconds of
one another, the Control panel will generate an
Alarm when the shortest Pre-Alarm Time of all the
Zones concerned expires.
Accepted values: 0 to 300 seconds (5 minutes), in steps
of 10 seconds.
Default setting: 60 seconds.
Investigation Time This field wilI allow you to program
an “interval” that will override the Pre-Alarm Time. This
“interval” will allow users time to investigate fire alerts.
It will be applied when the Ack/Evac. key is pressed for
less than 5 seconds at Access Level 2 (Keyswitch
ENABLED or PIN Code entered).
Accepted values: 0 to 300 seconds (5 minutes), in steps
of 10 seconds
Default value: 60 seconds.
Outputs
The Outputs page controls the pulse pattern for
Pre-Alarm (Alert) and/or Alarm (Evacuate) signalling on
the NAC1 and NAC2 outputs, and Alarm (Evacuate) si-
gnalling on the ALARM output.
The pattern is represented by a series of bells, each bell
representing a second.
The configuration of the RED and WHITE backgrounds
(for On and Off respectively e.g. all RED indicates conti
-
nuously On) determines the respective pulse pattern.
For example, the output devices (connected to
NAC1and NAC2) can be configured to have one audi
-
ble output for Pre-Alarm (Alert) and a different audible
output for Alarm (Evacuate), thus allowing users to di
-
stinguish between the two conditions, as follows.
n
NAC1 Output
Pre-Alarm pattern The bell chart will allow you to pro
-
gram the Pre-Alarm (Alert) pattern of NAC1.
Ø
= Output OFF for 1 second;
Ø
= Output ON for 1 second.
Pre-Alarm Default setting: NAC1 will turn ON for 2 se
-
conds then turn OFF for 6 seconds.
Alarm pattern To be set up in the same way as the
Pre-Alarm pattern of NAC1 but for the Alarm pattern.
Default setting: NAC1 is continuous.
40 Conventional Fire Panels J424/J408

Table of Contents

Related product manuals