Loading...
Type in the Extinguishment Termination Code than
press the Disable Extinguish. button to stop the Extin
-
guishment Time.
+
When the Extinguishment Termination Code is en
-
tered, this will be acknowledged by 5 beeps in ra
-
pid succession. The Extinguishment Termination
Code may only be entered at Access Level 1. After
20 seconds, the Extinguishment Termination Code
will no longer have any effect (double beep).
n
Night Mode Silence Time
This parameter determines how long the Control panel
will hold “Silence” status during Night Mode.
Accepted values: 0 through 600 seconds (10 minutes),
in steps of 5 seconds
Default setting: 60 seconds
n
Mains Failure Signalling Delay
This parameter determines how long the Control panel
will wait before signalling a Mains Failure event.
Accepted Values: 0 through 30 minutes, in steps of 1
minute.
Default Setting: 0 minutes.
n Date/Time
This field is for the current date and time.
Downloading
Once the operating parameters have been set up, they
must be downloaded to the respective Control Panel,
as follows.
1. Remove the screws 4 and open the Control panel.
2. Connect the jumper 65 to the first and second ter
-
minal pins on the 3-pin terminal strip marked PRG
on the Main Board. All the Control panel LEDs will
go OFF except for the Disab./Fault Telecom LED
which will blink to indicate that the system is re
-
ady for programming via computer.
3. Connect the Control Panel serial port (67) to one of
the PC serial ports, as follows:
using a CVSER/9F9F link (accessory item), or a
cable similar to the one in Figure 28a;, connect the
Control Panel to the PC;
if the PC serial port has 25 pins, use an
ADSER/9M25F adapter (accessory item), or a ca
-
ble similar to the one in Figure 28b.
4. Select the PC serial port used for connection with
the Control panel, as follows:
select Serial Ports from the Setup menu;
select the serial port (Control Panel section);
click or OK.
5. Select the parameters to be downloaded, as fol-
lows:
select Control panel from the Setup menu;
select the Control panel type from the Panel
menu;
select the respective firmware release from the
Firmware menu;
click OK.
PROGRAMMING FROM A PC 43
5
4
6
5
4
3
2
1
9
18
8
19
17
16
15
14
7
20
21
22
23
24
25
6
3
7
2
8
9
10
11
12
13
1
DB9 Female
connector
a)
b)
7-wire cable
shield
DB25 Female
connector
5 5
4 4
9 9
8 8
7 7
6 6
3 3
2 2
1 1
DB9 Female
connector
7-wire cable
shield
DB9 Female
connector
Figure 28 Wiring diagram for the serial link between the Control panel and PC