Pre-extinguishment Phase
If the programmed extinguishment conditions occur
(programmed by your Installer), the Extinguishment
Module will generate the Pre-extinguishment phase
which will be signalled by:
Ø
the respective signalling devices;
Ø
the ON Pre Ext. LED (On).
Ø
buzzer.
The Extinguishment Module will activate the Fire Extin
-
guishment systems when the Pre-extinguishment Time
expires.
The Pre-extinguishment phase will allow you to check
whether use of Fire Extinguishment systems, and Eva
-
cuation of the premises are really necessary.
You can end this phase by pressing:
Ø
any “Stop Extinguishment” button (set up by your
Installer).
In this case, the Pre-Extinguishment Time will NOT be
stopped by the Control panel. When the time has elap
-
sed, no extinguishment will occur unless the IE Input is
restored to stanby.
+
The Disable Extinguish. button can be used du
-
ring Access Level 2 only.
n Extinguishment Phase
The Extinguishment Module will activate the Fire Extin-
guishment systems when the Pre-extinguishment Pha-
se expires.
The Extinguishment Phase will be signalled by.
Ø the ON Electrovalve LED (On).
Ø the devices provided by the installer.
Ø buzzer.
The AV ACTIVATED event, and the respective details
will be recorded in the logger (EXTING.MODULE 1 or
EXTING.MODULE 2).
The Extinguishment Phase will run for the pre-set Extingui
-
shment Time or until the Control panel Resets.
n
Manual Extinguishment
The Extinguishment Module can be activated from ma
-
nual call-points (ask your Installer for details).
Manual activation of the Extinguishment Module is si
-
gnalled by:
Ø
the ON Manual Ext. LED (On);
Ø
a message on the display similar to the following:
EXTING.MODULE.1
MANUAL ACTIVATE
Ø
buzzer.
+
If you activate the Extinguishment Module ma
-
nually, the Control panel will generate an Alarm.
+
Pre-Extinguishment and Extinguishment will NOT
be carried out by the Control panel in the event of a
fault on the PR Output or the IE Output.
n
Disable Extinguish. button
This button will allow you to inhibit the Fire Extingui
-
shment systems.
+
The Disable Extinguish. button can be used du
-
ring Access Level 2 only.
This operation will be signalled by:
Ø
the Disable Extinguish. LED (On);
Ø
the Disab. LED (On).
The OUTS BYPASS event, and respective details will
be recorded in the logger (EXTING.MODULE 1 or
EXTING.MODULE 2).
If you disable the Extinguishment Module during
Standby status, it will be unable to operate in the event
of an Alarm.
n
Disable Manual Extinguish. button
This button will allow you to Disable/Enable manual ac
-
tivation of the Extinguishment Module.
+
The Disable Manual Extinguish. button can be
used during Access Level 2 only.
This operation will be signalled by:
Ø the Disable Manual Extinguish. LED (On);
Ø the Disab. LED (On).
n Disable Automatic Extinguishment
This button will allow you to Disable/Enable the activa-
tion of extinguishment, via the detectors provided by the
installer.
+
The Disable Automatic Extinguish. button can
be used during Access Level 2 only.
This operation will be signalled by:
Ø
the Disable Automatic Extinguish. LED (On);
Ø
the Disab. LED (On).