MANUAL for the basic control panel | CCB2.0
29
8.3. Stages Conf.
Not available in the Basic Control Panel 2.0 (CCB2.0).
Staged regulation is only available in the Stages Control Panel 2.0 (CCE2.0).
Note 1: This setting must be set to "NO" for the recirculation pump to start.
8.4. 0...10V o 4...20 mA Conf.:
Not available in the Basic Control Panel 2.0 (CCB2.0).
Staged regulation is only available in the Stages Control Panel 2.0 (CCE2.0).
8.5. UV lamp configuration
Switches the UV water treatment system on or off:
Enabled (1)
Disabled (0)
Note 1: If the UV lamp is installed immersed in the basin, a bridge must be made in J18 (IN1)
Note 2: Each time the UV lamp is switched on, an internal 12,000 hr operating counter is activated,
only when the equipment is running. After these 12,000 hours of operation, the E51 error is triggered
to replace the lamp.
Note 3: After the lamp is replaced following an E51 error, the 12,000-hour counter must be reset by
switching the lamp off (0) and on (1) in this configuration menu.
8.6. Conf. 1-3 PHASES
Select whether you have a single-phase or three-phase power
supply.