9.3. TIMER T02 (ex SW1 CD)
Enter the time between partial emptying of the basin with
conductivity control.
The Timer range is from 1 min to 15 min.
The factory set value is 5 min.
9.4. TIMER T03 (ex SW2 AB)
Enter the complete emptying confirmation time. This is the
maximum time for the level sensor to confirm the minimum water
level or obstruction of the drain after the emptying command.
The Timer range is from 1 min to 60 min.
The factory set value is 10 min.
9.5. TIMER T04 (ex SW2 CD)
Enter the additional complete emptying time, during which the
emptying motor valve will be open.
The Timer range is from 30 min to 400 min.
The factory set value is 60 min.
9.6. TIMER T05 (ex SW3 AB)
Enter the complete emptying frequency during operation.
The Timer range is from 0 min to 24 h.
The factory set value is 0 min.
0 min = never