Electrical Installation Tester
Specifications
11
Tripping Speed Test (
∆
T)
RCD Current Selection
Test Function
10 mA 30 mA 100 mA
[1]
300 mA
[1]
500 mA
[1]
1000 mA
[2]
var
[3]
x ½, 1
√ √ √ √ √ √ √
x 5
√ √ √
Ramp
√ √ √ √ √ √ √
Auto
√ √ √
Notes
Mains voltage 100 V – 265 V ac, 50/60 Hz
[1] Type B RCDs require mains voltage range of 195 V – 265 V.
[2] Type AC RCDs only.
[3] Type A RCDs are limited to 700 mA, not available for Type B RCDs.
Measurement Range
Current
Multiplier
*RCD Type
Europe UK
Trip Time Accuracy
x ½ G 310 ms 2000 ms
±(1 % Reading + 1 ms)
x ½ S 510 ms 2000 ms
±(1 % Reading + 1 ms)
x 1 G 310 ms 310 ms
±(1 % Reading + 1 ms)
x 1 S 510 ms 510 ms
±(1 % Reading + 1 ms)
x 5 G 50 ms 50 ms
±(1 % Reading + 1 ms)
x 5 S 160 ms 160 ms
±(1 % Reading + 1 ms)
Notes
*G – General, no delay
*S – Time delay
Maximum Trip Time
The RCD * symbol switches on when testing the RCD trip time if the trip time meets the following conditions:
RCD I
ǻ N
Trip Time Limits
AC G, A, B x 1 Less than 300 ms
AC, G - S type, A - S type, B - type x 1 Between 130 ms and 500 ms
AC G, A, B x 5 Less than 40 ms
AC, G - S type, A - S type, B - type x 5 Between 50 ms and 150 ms
RCD/FI-Tripping Current Measurement/Ramp Test (I
∆
N
)
Dwell Time
Current Range Step Size
Type G Type S
Measurement
Accuracy
30 % to 110 % of
RCD rated current
[1]
10 % of I
∆ N
[2]
300 ms/step 500 ms/step
±5 %
Notes
[1] 30 % to 150 % for Type A I
ǻ N
>10 mA
30 % to 210 % for Type A I
ǻ N
= 10 mA
20 % to 210 % for Type B
Specified trip current ranges (EN 61008-1):
50 % to 100 % for Type AC
35 % to 140 % for Type A (>10 mA)
35 % to 200 % for Type A (≤10 mA)
50 % to 200 % for Type B
[2] 5% for Type B