165X
Users Manual
34
Measuring Earth Resistance (Model 1653 Only)
.
R
E
apx010f.eps
Figure 18. Earth Resistance Display/Switch and
Terminal Settings
The earth resistance test is a 3-wire test consisting of two
test stakes and the earth electrode under test. This test
requires an accessory stake kit. Connect as shown in
Figure 19.
Best accuracy is achieved with the middle stake at
62% of the distance to the far stake. The stakes
should be in a straight line and wires separated to
avoid mutual coupling.
The earth electrode under test should be
disconnected from the electrical system when
conducting the test. Earth resistance testing should
not be performed on a live system.
62% L
L
PE (E)
Earthing rod
under test
N (S)
L (H)
apx014f.eps
Figure 19. Earth Resistance Test Connection
To measure earth resistance
1. Turn the rotary switch to the R
E
position.
2. Press and release T. Wait for the test to complete.
The primary (upper) display shows the earth
resistance reading.
Voltage detected between the test rods will be
displayed in the secondary display. If greater
than 10 V, the test is inhibited.