Electrical Installation Tester
Specifications
53
Tripping Speed Test (
∆
T)
Models 1652 and 1653
Current Settings Multiplier Current Accuracy
10–30–100–300-500-1000 mA x ½ +0% -10% of test current
10–30–100–300-500-1000 mA x 1 +10% -0%
10-30 mA x 5 +10%
Measurement Range
Current Multiplier *RCD Type
Europe UK
Trip Time Accuracy
x ½ G 310 ms 2000 ms +(1% Reading + 1 digit)
x ½ S 510 ms 2000 ms +(1% Reading + 1 digit)
x 1 G 310 ms 310 ms +(1% Reading + 1 digit)
x 1 S 510 ms 510 ms +(1% Reading + 1 digit)
x 5 G 50 ms 50 ms +(1% Reading + 1 digit)
x 5 S 160 ms 160 ms +(1% Reading + 1 digit)
*G – General, no delay
*S – Time delay