EasyManua.ls Logo

Fluke 165X - Testing Phase Sequence

Fluke 165X
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical Installation Tester
Making Measurements
35
Testing Phase Sequence (Model 1653 Only)
.
apx011f.eps
Figure 20. Phase Sequence Display/Switch and
Terminal Settings
Use the connection shown in Figure 21 when making a
phase sequence test connection.
L1
L2
L3
PE (L2/Green)
L (L1/Red)
N (L3/Blue)
apx022f.eps
Figure 21. Phase Sequence Test Connection
To perform a phase sequence test
1. Turn the rotary switch to the Q position.
2. The primary (upper) display shows:
123 for correct phase sequence.
321 for reversed phase sequence.
Dashes (---) instead of numbers if insufficient
voltage is sensed.