Electrical Installation Tester
Making Measurements
21
Measuring Insulation Resistance
.
R
ISO
apx005f.eps
Figure 8. Insulation Resistance Display/Switch and
Terminal Settings
XW Warning
Measurements should only be performed on
de-energized circuits.
To measure insulation resistance
1. Turn the rotary switch to the R
ISO
position.
2. Use the L and PE (red and green) terminals for this
test.
3. Use the 4 to select the test voltage. Most insulation
testing is performed at 500 V, but observe local test
requirements.
4. Press and hold T until the reading settles and the
tester beeps. For most tests you will want to use the
probe with the remote control T button.
Note
Testing is inhibited if voltage is detected in the
line.
The primary (upper) display shows the insulation
resistance.
The secondary (lower) display shows the actual
test voltage.
Note
For normal insulation with high resistance, the
actual test voltage (
U
N
) should always be equal
to or higher than the programmed voltage. If
insulation resistance is bad, the test voltage is
automatically reduced to limit the test current to
safe ranges.