EasyManua.ls Logo

Fluke 7008 - Linefeed; IEEE-488 Parameters Menu; IEEE-488 Address

Fluke 7008
78 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7008
Users Guide
9-14
9.12.4 Linefeed
The final parameter in the serial interface menu is the linefeed mode. This
parameter enables (on) or disables (off) transmission of a linefeed character (LF,
ASCII 10) after transmission of any carriage-return. The linefeed parameter is
indicated by,
LF Serial linefeed parameter
Press “SET” to access the linefeed parameter.
LF= On Current linefeed setting
The mode may be changed using “UP” or “DOWN” and pressing “SET”.
LF= OFF New linefeed setting
9.13 IEEE-488 Parameters Menu
Baths may optionally be fitted with an IEEE-488 GPIB interface. In this case the
user may set the interface address within the IEEE-488 parameter menu. This
menu does not appear on baths not fitted with the interface. The menu is
indicated by,
IEEE IEEE-488 parameters menu
Press “SET” to enter the menu.
9.13.1 IEEE-488 Address
The IEEE-488 interface must be configured to use the same address as the
external communicating device. The address is indicated by,
AddrESS IEEE-488 interface address
Press “SET” to access the address setting.
Add= 22 Current IEEE-488 interface address
Adjust the value with “UP” or “DOWN” and then use “SET” to set the address to
the displayed value.
Add= 15 New IEEE-488 interface address

Table of Contents

Related product manuals