EasyManua.ls Logo

Fourgroup Full-App 2 - 10. GENERAL SETTINGS; Dry Running Alarm Restart Setting 4 and Exclusion; Display Timeout and Password Setting

Fourgroup Full-App 2
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
To move to the next horizontal parameter press the button
:
To move to the next horizontal parameter press the button
:
To move to the next horizontal parameter press the button
:
Restart Setting
Restart4 XXX min
Restart Setting
Restart3 XXX min
Exclude Restart
0=NO 1=YES ->X
Restart Setting
Restart4 XXX min
The parameter “Restart Setting, Restart 4”, as previous 3 parameters, is related to the dry
running alarm. It is possible to set the timer delay for the automatic restart after the 4th dry
running alarm . If the alarm for Dry condition is still detected after the first three restarts of the
pump the pump will be restarted again using the time setting restart setting ,restart 4. The
delay time value being set is valid for all the pumps installed.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 999 minutes and it’s independent from restart time 3.
Factory default setting: 90 minutes.
Exclude Restart
0=NO 1=YES ->X
Restart Setting
Restart4 XXX min
Light Display
Off XXXsec
Esclus. Ripart.
0=NO 1=SI ->X
The parameter “Exclude Restart” will set the command for the control panel to continue to
make restarts after the 4
th
one or to stop restarting.
0=NO: setting “0” the control panel will continue to restart the pumps with the 4
th
timer delay
setting (i.e. restart the pumps at intervals equal to the parameter set in the “Restart Setting,
Restart 4”) infinitely.
1=YES setting “1” after the 4
th
restart of the pump, if the alarm for dry condition is still active
the control panel will stop the operation of the pump (or pumps) and it will wait for the
“operator manual reset” (manual operation to control the conditions of the system).
The “X” indicates the setting of the parameter to modify.
Factory default setting: 0.
Light Display
Off XXXsec
Esclus. Ripart.
0=NO 1=SI ->X
Setting
Password XXXX
Light Display
Off XXXsec
The parameter “Light Display Off” will set the amount of time of inactivity before the display will
turn off automatically (power saving mode) from the last button pressing. If the display is
momentarily off in power saving mode, it will go back on after pressing any button.
Note: pressing of buttons
, , will not have any effect on the operation of program
settings of full-app2; however, pressing other buttons could modify the operations of the
pumps.
The “X” indicates the setting of the parameter to modify.
The range of value is from 5 to 250 seconds.
Factory default setting: 60 seconds.
Note: It is not possible to keep the display always On (maximum 250 seconds after last button
pressing).
Setting
Password XXXX
Light Display
Off XXXsec
Sel.Language: X
1=I 2=EN 3=E 4=F