EasyManua.ls Logo

Fourgroup Full-App 2 - 10. GENERAL SETTINGS; Language Selection for Alarms; Delay After Power Return Configuration; Enable 4-20 mA Input Activation

Fourgroup Full-App 2
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
Once entered in the programming mode the first horizontal menu will be:
Pressing
and navigate the horizontal menus. With the button displays the corresponding vertical parameter:
To move to the next horizontal parameter press the button
(as indicated in the flow-chart attached to this manual as
an example, the menu structure of the horizontal parameter is circular; therefore, by pressing the buttons
or the
button
to display the following parameter; to facilitate the descriptions of the parameters settings the manual will
show the navigation inside the various menus:
To move to the next horizontal parameter press the button
:
10. GENERAL SETTINGS
The parameter “Select Language” will set the language selection for the alarm messages to be
displayed (the “X” indicates the position of the parameter to modify):
1=Italian; 2=English; 3=Spanish; 4=French.
Factory default selection: 1-Italian.
General
settings
Press Enter to
Set-up Exit
Settings pumps
Delay Power ret.
0=RND XXXsec
Sel.Language: X
1=I 2=EN 3=E 4=F
Enable 4-20mA
0=NO 1=YES X
Delay Power ret.
0=RND XXXsec
The parameter “Delay after Power Return” will set the timer delay to wait before reactivating
the control panel after a power-cut.
The “X” indicates the digit of the parameter to modify:
The settable range value is from 0 to 999 seconds.
0: setting the value to “0” (0=RND, random) will set the timer delay to a random value
automatically (the timer value will be between 1 and 999 seconds) by the control panel at every
restart after every power-cut (this function is useful in a station with several control panels full-
app and it’s not desired the simultaneous reactivation of several control panels).
Default setting: 3 seconds.
Note: the delay timer to reactivate of the control panel is displayed as a countdown timer to the
restart after power-cut. During the countdown the operating functions are inhibited. Therefore,
it’s not possible to operate the display/settings also it is not possible to use for programming
mode, nor manual operation.
Enable 4-20mA
0=NO 1=YES X
Delay Power ret.
0=RND XXXsec
Hi.Flt.Pumps ON
0=NO 1=YES X
Enable 4-20mA
0=NO 1=YES X
The parameter “Enable 4-20mA” will allow to activate/deactivate the use of the reading device
with signal 4-20mA (for example, pressure transducer, piezoresistive sensor, ultrasounds
sensor, etc…). The activation of input 4-20mA allows the use of working in operating mode
“DIGIT”. It is possible to utilize the 4-20mA device even as simple monitor of levels and usage
of relative alarms.
The “X” indicates the position of the parameter to modify:
0=NO: input 4-20mA DISABLE.
1=YES: input 4-20mA ENABLE.
Factory default setting: 0 (DISABLE).
General
settings
Sel.Language: X
1=I 2=EN 3=E 4=F

Related product manuals