PROGRAMMING CODES
Code Entry
1. Swipe the magnet at C1. Each of the bottom row of LEDs turns on one at a time.
2. Swipe the magnet at C2. Each of the top row of LEDs turns on one at a time.
For example:
A. To enter Code 32, swipe the magnet at C1 three times, and then swipe the
magnet at C2 twice.
B. If the code is accepted, the display will ash with the corresponding
number of top and bottom LEDs as the entered count. For example—three
bottom row and two top row LEDs will ash alternately between the top and
bottom rows.
3. The process times out after 10 seconds of inactivity, or if no additional codes
are entered (except for the non linear calibration).
4. Save the new setting or enable new data entry by holding the magnet at C2 for
5 seconds.
Calibration and Tank Level Correction
Linear Tank Calibration
1. Start this process with a full tank.
2. Enter Code 44 to activate the Linear tank calibration. (See page 23 for detailed
step-by-step instructions.)
Nonlinear Tank Calibration
1. Start this process with an empty tank.
2. Enter Code 33 to activate the Nonlinear tank calibration. (See page 22 for
detailed step-by-step instructions.)
Level Correction and Warning
Enter Code 55 to start full level correction. Make sure the tank is almost full, or
at greater than 90%.
Enter Code 66 to activate the warning, if the signal is 0.5V higher than the full level.
Note: See page 27 for complete Diagnostics & Warnings information.