Brightness Adjustment
Code 31 Day time brightness. Default—Brightness Level - 8
Code 32 Night time brightness. Default—Brightness Level - 2
1. Every magnet swipe at C 1 will incrementally increase/decrease the
brightness for 10 various levels.
2. Starting from the lowest level, repeat the process from number 1.
3. Enable the data entry by holding the magnet at C 2 for 5 seconds.
4. Adjust the brightness to the desired level.
5. Save the new setting by holding the magnet at C 2 for 5 seconds.
Primary and Remote Synchronization
If the level pressure sensor is detected, (0.3V or more) the unit will work as a
Primary display. Any remote unit including Water, Foam A, or Foam B, and MaxVision,
that is connected via CAN bus will be synchronized with following settings:
Tank level calibration
Display Pattern
Warning and control activation levels
NOTE: Brightness will remain as adjusted locally in the remote display unit.