Warning and Control Level Adjustment
Code 21 To set the Audio warning level. Default—1/4 (25%)
Code 22 To set the Visual warning level. Default—1/4 (25%)
Code 23 To set the "Tank Full" audio signal level.
Default—disabled.
Code 24 To set the Valve control signal "Low" activation level.
Default— 1/2 (50%)
Code 25 To set the Valve control signal "Full" deactivation level.
Default —7/8 (95%)
Code 26 To set the level for Audio warning to be turned off (or disabled).
Default —1/4 (25%)
Code 27 To set the level for Visual warning to be turned off.
Default —1/4 (25%)
Code 28 To set the delay time in seconds before the Audio warning is activated.
Default —1 second (NOTE: each LED delays the Audio warning
activation by 1 second. This is adjustable from 1 to 7 seconds. )
1. Enable the data entry by holding the magnet at C 2 for 5 seconds. This sets the
desired level for either Warnings or Valve Control setting activation.
2. Wait ve seconds.
3. Save the new setting by holding the magnet at C 2 for 5 seconds.
Note: If the WL300 is set with code 24 and 25, the buzzer output will work
as a valve controller.