Full Tank Correction (Code 55)
This ne calibration procedure is used to ne tune the tank display after a
non-linear or linear calibration has been completed. The calibration process requires
that the tank be full at the start of the procedure and the display shows 75% or more.
The term ‘swipe’ means to move the magnet up to and then away from the
C 1 or C 2 sensors on front of the display.
Note: To exit the calibration mode without saving any new calibration, reset
the power to the display.
1. Fill the tank. (Do not ll up into the ll tower.)
2. Apply power to the display module.
Note: Once the calibration program is activated there is a six second time
out. Do not wait more than six seconds to move from step 3 to step 4.
3. Swipe the magnet ve times at C 1 and ve times at C 2 to enter the
calibration mode.
Result: Top and bottom ve display LEDs ash on and off.
4. After three seconds hold the magnet at C 2 for ve seconds to set the calibration
into memory.
5. After six seconds the calibration process will terminate and all the LEDs will
go on to show that the tank is full.