Troubleshooting
General faults in power supply
Page 38
B 067 03 11_en v
5
5 Troubleshooting
5.1 General faults in power supply
Error characteristics Cause of error Error correction
Nothing is shown on the
display
No power to the controller
General power failure
FI circuit breaker or line
protection is switched off
Main switch is turned off
Faulty glass tube fuse in the
controls
Switch on the FI circuit breaker or
line protection
Switch on the main switch
Switch off the main switch
Replace fuse – note current
(e.g. 10A)
Switch on the main switch
5.1.1 System procedure following power failure
When the power supply has been restored the boiler returns to the
previously specified mode and is controlled according to the specified
program.
5.2 Excessive temperature
The safety temperature limiter (STL) shuts down the boiler when it
reaches a temperature of max. 105°C. After the boiler has cooled down,
the safety temperature limiter must be manually unlocked:
Unscrew the cap on the safety temperature limiter (2)
Reset the safety temperature limiter by pressing with a screw-driver.
Replace the cap
2