AC input/output data
Nominal frequency for Full Backup
53 / 63 Hz 
1)
Initial short circuit alternating cur-
rent / phase I
K
45.5 A
Total harmonic distortion < 3%
Power factor cos phi 
2)
0.8 - 1 (adjustable)
Max. permitted mains impedance Z
max
at PCC
 4)
None
Maximum output fault current / dura-
tion
29 A / 3 ms
AC output data PV Point
Max. output power 4133 W (for 5 s)
Rated power 3000 W
Nominal output current 13 A
Nominal grid voltage 1 ~ NPE 220 V / 230 V / 240 V
Nominal frequency
53 / 63 Hz 
1)
Switching time < 90 s
Power factor cos phi 
2)
0 - 1
AC output data Full Backup
Max. output power 13,780 W (for 5 s)
Rated power 10,000 W
Nominal output current 43.5 A
Nominal grid voltage
 
1 ~ NPE 220 V
1 ~ NPE 230 V
1 ~ NPE 240 V
Nominal frequency for Full Backup
53 / 63 Hz 
1)
Switching time < 90 s
Power factor cos phi 
2)
0 - 1
General data
Maximum efficiency 97.3%
European efficiency (U
mpp nom
) 97%
European efficiency (U
mpp max
) 96.5%
European efficiency (U
mpp min
) 96.6%
Self-consumption at night 9 W
Cooling Controlled forced-air ventilation
Protection class IP 66
Dimensions H x W x D 595 × 529 × 180 mm
Weight 23.5 kg
175