Ground electrode terminal (6-pin)
Select a sufficiently large cable cross section based on the actual device output.
4
2.5-10 mm
2
AWG 14-8
2.5-10 mm
2
AWG 14-8
2.5-10 mm
2
AWG 14-8
2.5-10 mm
2
AWG 14-8
2.5-10 mm
2
AWG 14-8
* According to product standard IEC 62109, the ground conductor must
correspond to the phase cross-section for phase cross-sections ≤16 mm²;
for phase cross-sections >16 mm², it must correspond to at least 16 mm².
** The cable cross section must be dimensioned in accordance with the in-
stallation situation and the specifications of the battery manufacturer.
Permissible
cables for the
data communic-
ation connection
Cables with the following design can be connected to the terminals of the invert-
er:
-
Copper: round, solid
-
Copper: round, fine-stranded
IMPORTANT!
Connect the individual conductors to an appropriate ferrule if several individual
conductors are connected to one input of the push-in terminals.
WSD connections with push-in terminal
Dis-
tance
max.
Strip-
ping
length
Cable re-
commenda-
tion
100 m
109 yd
10 mm
0.39 inch
0.14-1.5 mm
2
AWG 26 - 16
0.14-1.5 mm
2
AWG 26 - 16
0.14-1 mm
2
AWG 26 - 18
0.14-1.5 mm
2
AWG 26 - 16
min. CAT 5
UTP (un-
shielded
twisted pair)
Modbus connections with push-in terminal
Dis-
tance
max.
Strip-
ping
length
Cable re-
commenda-
tion
300 m
328 yd
10 mm
0.39 inch
0.14-1.5 mm
2
AWG 26 - 16
0.14-1.5 mm
2
AWG 26 - 16
0.14-1 mm
2
AWG 26 - 18
0.14-1.5 mm
2
AWG 26 - 16
min. CAT 5
STP (shiel-
ded twisted
pair)
IO connections with push-in terminal
Dis-
tance
max.
Strip-
ping
length
Cable re-
commenda-
tion
30 m
32 yd
10 mm
0.39 inch
0.14-1.5 mm
2
AWG 26 - 16
0.14-1.5 mm
2
AWG 26 - 16
0.14-1 mm
2
AWG 26 - 18
0.14-1.5 mm
2
AWG 26 - 16
Single con-
ductor pos-
sible
LAN connections
Fronius recommends at least CAT 5 STP (shielded twisted pair) cables and a maximum distance of
100 m (109 yd).