Nominal frequency
50 / 60 Hz
1)
Nominal frequency for Full Backup
53 / 63 Hz
1)
Total harmonic distortion < 2%
Power factor cos phi
2)
0.8 - 1 (adjustable)
Max. permitted mains impedance Z
max
on PCC
4)
None
Maximum output fault current / dura-
tion
29 A / 3 ms
AC output data PV Point
Max. output power 4133 W (for 5 s)
Rated power 3000 W
Nominal output current 13 A
Nominal grid voltage
1 ~ NPE 220 V / 230 V / 240 V
Nominal frequency
53 / 63 Hz
1)
Switchover time < 90 s
Power factor cos phi
2)
0 - 1
AC output data Full Backup
Max. output power 4133 W (for 5 s)
Rated power 3000 W
Nominal output current 13 A
Nominal grid voltage
1 ~ NPE 220 V
1 ~ NPE 230 V
1 ~ NPE 240 V
Nominal frequency for Full Backup
53 / 63 Hz
1)
Switchover time < 90 s
Power factor cos phi
2)
0 - 1
General data
Maximum efficiency 97.6%
European efficiency (U
mpp nom
)
96.8%
European efficiency (U
mpp max
)
95.9%
European efficiency (U
mpp min
)
95.3%
Self-consumption at night
8.2 W
Cooling Controlled forced-air ventilation
Protection class IP 66
Dimensions H x W x D 530 × 474 × 165 mm
Weight 17 kg
Inverter topology Non-insulated transformerless
Permitted ambient temperature -40 °C – +60 °C
Permissible humidity 0–100% (incl. condensation)
155
EN