EasyManuals Logo

Fronius Primo GEN24 3.0 User Manual

Fronius Primo GEN24 3.0
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #162 background imageLoading...
Page #162 background image
Input currents of digital inputs depending on the input voltage;
input resistance = 70 kOhm
Total power for digital output
(internal supply)
6 W at 12 V (USB not connected)
Power per digital output
(external supply)
1 A at >12.5 V-24 V
(max. 3 A in total)
Datalogger/web server Integrated
Fronius Primo
GEN24 4.6 / 4.6
Plus
DC input data
MPP voltage range
(at rated power)
230 - 530 V
Max. input voltage
at 1000 W/m²/-10 °C in an open cir-
cuit
600 V
Min. input voltage 65 V
Feed-in start-up input voltage in grid
operation
5)
80 V
Max. input current
PV 1
PV 2
22.0 A
12.0 A
Max. short circuit current of solar
modules (I
SC PV
)
PV 1
PV 2
33 A
18 A
Max. short circuit current
(I
SC PV1
+ I
SC PV2
= I
SC max
)
Total
51 A
Max. inverter backfeed current to the
array
3)
33 / 18 A
Number of inputs - PV 1 2
Number of inputs - PV 2 2
Max. capacity of the PV generator
against earth
920 nF
DC input data battery
Max. voltage 455 V
Min. voltage 150 V
Max. current 22 A
Max. output 4600 W
DC inputs 1
AC input/output data
Nominal output power (P
nom
) 4600 W
Max. output power 4600 W
Rated apparent power 4600 W
162

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius Primo GEN24 3.0 and is the answer not in the manual?

Fronius Primo GEN24 3.0 Specifications

General IconGeneral
Max. apparent AC power3.0 kVA
Max. output current (at AC nom. voltage)13.0 A
AC voltage range180 - 280 V
Frequency50 / 60 Hz
THD< 3 %
Max. input current (DC)12.5 A
Max. input current per MPP tracker12.5 A
Protection classIP66
AC Nominal Power3.0 kW
Operating Temperature Range-25 - 60 °C
Warranty10 years