7) The sum of the rated power per phase must not exceed the rated power of
the inverter.
8) Valid for Fronius Primo GEN24 with battery connection and Fronius Primo
GEN24 Plus.
Integrated DC
disconnector
General data
Product name Benedict LS32 E 7905
Rated insulation
voltage
1000 V
DC
Rated impulse with-
stand voltage
8 kV
Suitability for isola-
tion
Yes, DC only
Utilization category
and/or PV utiliza-
tion category
according to IEC/EN 60947-3 Category of utilization
DC-PV2
Rated short-time
withstand current
(I
cw
)
Rated short-time withstand current (I
cw
): 1000 A
Rated short-circuit
making capacity
(I
cm
)
Rated short-circuit making capacity (I
cm
): 1000 A
Rated operational current and rated breaking capacity
Rated operational
voltage (U
e
)
Rated opera-
tional current
(I
e
)
I
(make)
/
I
(break)
rated operation-
al current (I
e
)
I
(make)
/
I
(break)
≤ 500 V
DC
14 A 56 A 36 A 144 A
600 V
DC
8 A 32 A 30 A 120 A
700 V
DC
3 A 12 A 26 A 88 A
800 V
DC
3 A 12 A 17 A 68 A
900 V
DC
2 A 8 A 12 A 48 A
1000 V
DC
2 A 8 A 6 A 24 A
Number of poles 1 1 2 2
171