Max. capacity of the PV generator
against earth
800 nF
DC input data battery
Max. voltage 455 V
Min. voltage 150 V
Max. current 22 A
Max. output 4000 W
DC inputs 1
AC input/output data
Nominal output power (P
nom
) 4000 W
Max. output power 4000 W
Rated apparent power 4000 W
Nominal grid voltage 1 ~ NPE 220V / 230V / 240 V
Min. grid voltage
155 V
1)
Max. grid voltage
270 V
1)
Max. output current 25.8 A
Current (inrush)
6)
20 A / 1.3 ms
Nominal frequency
50 / 60 Hz
1)
Nominal frequency for Full Backup
53 / 63 Hz
1)
Total harmonic distortion < 2%
Power factor cos phi
2)
0.8 - 1 (adjustable)
Max. permitted mains impedance Z
max
on PCC
4)
None
Maximum output fault current / dura-
tion
29 A / 3 ms
AC output data PV Point
Max. output power 4133 W (for 5 s)
Rated power 3000 W
Nominal output current 13 A
Nominal grid voltage 1 ~ NPE 220 V / 230 V / 240 V
Nominal frequency
53 / 63 Hz
1)
Switchover time < 90 s
Power factor cos phi
2)
0 - 1
AC output data Full Backup
Max. output power 5510 W (for 5 s)
Rated power 4000 W
Nominal output current 17.4 A
Nominal grid voltage
1 ~ NPE 220 V
1 ~ NPE 230 V
1 ~ NPE 240 V
160