Electrical tests
Ground con-
ductor resistance
- The device to be tested must be safely isolated from the AC mains supply. The
mains lead (L1, N, PE) must not be connected. Follow the safety rules.
- The device to be tested must be safely isolated from the battery. The charging leads
must not be connected.
- There must be no earthing connections present
- No additional options should be connected to the battery charging system
- The device must be isolated from the PC and other connections
1 Measuring device
2 Battery charging system
9 Measuring line
Example: measuring the ground conductor resistance
- The measurement is taken between the ground terminal of the device and every
conductive part that can be touched and that is connected to the ground conductor.
- Should the original mains cable be with the battery charging system, the measure-
ment must be taken between the earthing of the mains cable and every conductive
part that can be touched and that is connected to the ground conductor. Move the
mains cable to detect any line breakage
- The resistance must not exceed 0.3 W *)
*) These requirements comply with DIN VDE 0701-0702 and ÖVE/ÖNORM E87011.
Also refer to the applicable requirements and standards in your country.