NOTE!
When connecting aluminum cables:
▶
Follow all national and international guidelines regarding the connection of
aluminum cables.
▶
Follow the instructions of the cable manufacturer, especially the note about
whether an annual check to ensure that the cables are firmly attached
should be performed.
NOTE!
Form a min. 4 in. (100 mm) cable loop with all cables.
NOTE!
To ensure that the inverter operates without any problems:
▶
Make sure that the grid's neutral conductor is grounded. For insulated net-
works (without grounding), this is not the case, and operation of the inverter
is not possible.
▶
A neutral conductor is required for measurement purposes when operating
the inverter. The neutral conductor must have a current carrying capacity of
at least 1 A.
Permitted
Cables
AC cables with the following design can be connected to the AC terminals of the
inverter:
-
Copper (Cu) or aluminum (Al): round, solid
-
Copper: round, stranded, up to conductor class 4
AC & DC = copper cables (Cu)
The following wire combinations can be used for wiring.
Select a sufficiently large cable cross-section based on the actual device output!
AWG
roun
d
AWG
stran
ded
AWG
stranded/round
AWG
round/round
AWG
stranded/stranded
4
2)
6
2)
6/6
4)
6/12
2
)
6/14
2
)
6/16
3
)
8
2)
8
1)
8/10
1
)
8/12
1
)
8/14
1
)
8/12
2
)
8/10
2
)
8/12
1
)
8/14
1
)
8/16
3
)
10
2)
10
1)
10/1
0
1)
10/1
2
1)
10/1
4
1)
10/1
0
1)
10/1
2
1)
10/1
4
1)
10/1
6
3)
12
2)
12
1)
12/1
0
1)
12/12
1)
12/1
4
1)
12/1
6
1)
12/1
0
1)
12/12
1)
12/1
4
1)
12/1
6
1)
14
2)
14
1)
14/1
0
1)
14/1
2
1)
14/1
4
1)
14/1
6
1)
14/1
0
1)
14/1
2
1)
14/1
4
1)
14/1
6
1)
27
EN-US