NOTE!
When connecting aluminum cables:
Follow all national and international guidelines regarding the connection of
aluminum cables.
Follow the instructions of the cable manufacturer, especially the note about
whether an annual check to ensure that the cables are firmly attached
should be performed.
NOTE!
Form a min. 4 in. (100 mm) cable loop with all cables.
NOTE!
To ensure that the inverter operates without any problems:
Make sure that the grid's neutral conductor is grounded. For insulated net-
works (without grounding), this is not the case, and operation of the inverter
is not possible.
A neutral conductor is required for measurement purposes when operating
the inverter. The neutral conductor must have a current carrying capacity of
at least 1 A.
Permitted
Cables
AC cables with the following design can be connected to the AC terminals of the
inverter:
Cu / Al Cu
-
Copper (Cu) or aluminum (Al): round, solid
-
Copper: round, stranded, up to conductor class 4
AC & DC = copper cables (Cu)
The following wire combinations can be used for wiring.
Select a sufficiently large cable cross-section based on the actual device output!
AWG
roun
d
AWG
stran
ded
AWG
stranded/round
AWG
round/round
AWG
stranded/stranded
4
2)
6
2)
6/6
4)
6/12
2
)
6/14
2
)
6/16
3
)
8
2)
8
1)
8/10
1
)
8/12
1
)
8/14
1
)
8/12
2
)
8/10
2
)
8/12
1
)
8/14
1
)
8/16
3
)
10
2)
10
1)
10/1
0
1)
10/1
2
1)
10/1
4
1)
10/1
0
1)
10/1
2
1)
10/1
4
1)
10/1
6
3)
12
2)
12
1)
12/1
0
1)
12/12
1)
12/1
4
1)
12/1
6
1)
12/1
0
1)
12/12
1)
12/1
4
1)
12/1
6
1)
14
2)
14
1)
14/1
0
1)
14/1
2
1)
14/1
4
1)
14/1
6
1)
14/1
0
1)
14/1
2
1)
14/1
4
1)
14/1
6
1)
27