IMPORTANT! If data communication cables are wired into the inverter, observe
the following points:
-
Provide separate conduits for data communication cables
-
Lay data communication cables in the supplied conduit
-
Knock out the appropriate opening
-
Cleanly deburr the knocked-out opening
-
Clip the inverter onto the mounting bracket
-
Guide the data communication cables through the cable glands from behind
-
When pivoting the inverter, ensure that the cables are not trapped, kinked, or
damaged in any other way. Do not loop the data communication cables.
-
Lay the data communication cables in the data communication area of the
inverter and connect to the Solar.Net “IN” and “OUT” connections.
Plug the termination plugs into the remaining Solar.Net connections.
Installing
Datamanager in
the Inverter
WARNING!
Danger of residual voltage from capacitors.
An electric shock can be fatal.
▶
Wait until the capacitors have discharged. Discharge takes 5 minutes.
WARNING!
An inadequate ground conductor connection can cause serious injury and dam-
age to property.
▶
The housing screws provide an adequate ground conductor connection for
grounding the housing and should not be replaced under any circumstances
by other screws that do not provide a reliable ground conductor connection.
IMPORTANT! Follow general ESD guidelines when handling option cards.
IMPORTANT! Only one Fronius Datamanager in master mode is permitted per
Fronius Solar.Net Ring. Switch other Fronius Datamanagers to slave mode or re-
move them.
Unused option card slots can be closed by replacing the cover (item number
42,0405,2094), or an inverter without Fronius Datamanager (light version) can be
used.
IMPORTANT! Only knock out one opening for the PC board when installing a
data manager in the inverter.