4-2
4.3 Configuring the Function Code Data Before Test Run
Configure the function codes listed below according to the motor ratings and your machinery design values. For
the motor ratings, check the ratings printed on the motor's nameplate. For your machinery design values, ask
system designers about them.
To set up function code, you need to use the keypad (option) or to access their data via communications link.
For details, refer to the FRENIC-Lift LM2C series Reference Manual.
Table 4.1 Configuring Function Code Data
code
Name Function code data Factory defaults
F04 Base Speed
Motor ratings
(printed on the nameplate of
the motor)
1500 (r/min)
F05
Rated Voltage at Base
380 (V)
P01* Motor (No. of poles)
4 (P)
P02 Motor (Rated capacity)
Nominal applied motor capacity.
P03 Motor (Rated current)
Rated current of nominal applied motor.
P06 Motor (No-load current)
No load current of the standard motor.
P07 Motor (%R1)
Primary resistance of the standard motor.
P08 Motor (%X)
Leakage reactance of the standard motor.
P12 Motor (Rated slip)
0.00 (Hz)
*1
*1 The rated slip of the standard motor is
applied.
F03* Rated Speed
Machinery design values
.
1450 (r/min)
F42
Selection 1
2 : Dynamic torque vector control
(Asynchronous motor)
C21* Speed Command Unit
0 : r/min (Speed data format)
L31* Elevator Parameter (Speed)
1000 (mm/s)
H190 Motor rotate direction
1 : Motor rotates in CW(Clockwise) direction
*
Recommend to start the setting by the following order C21, P01, F03 and L31, etc.
・In any of the following cases, motor auto-tuning (P04) is necessary because the standard settings of
motor parameters for Fuji motors are not applicable:
- The motor to be driven is not a Fuji product or is a non-standard product.
- The cabling between the motor and the inverter is long.
- A reactor is inserted between the motor and inverter.
For details of motor tuning procedure refer to the FRENIC-Lift LM2C series Reference Manual.