Carrier frequency automatic DEC function
Item
Output phase loss protection
Data
Input phase loss protection *)
0
OFF
OFF
OFF
1
ON
OFF
OFF
2
OFF
OFF
ON
3
ON
OFF
ON
4
OFF
ON
OFF
5
ON
ON
OFF
6
OFF
ON
ON
7
ON
ON
ON
STOP key priority function
Item
Data
Start check function
0
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
Function Settings
High Performance Functions: H Codes
0 : Manual set value 1 : Return to factory set value
2 : Motor parameter initializing (Motor 1)
--
0Data Initializing
(Data reset)
0 : Inactive,1 to 10 times 1 Times 0
0.5 to 20.0s
0.1 s 5.0
Retry
(No. of retries)
(Latency time)
(Function selection)
0 : Inactive
1 : Active (2 HP or more)
--
0Cooling Fan ON/OFF
0 : Inactive (linear) 1 : S-curve (weak) 2 : S-curve (strong) 3 : Non-linear
--
0
Gradual Acceleration/ Deceleration
0 : Inactive
1 : Active
--
1
Instantaneous Overcurrent Limiting
0.00 to 5.00V
0.01 V 1.60
(Level)
0 : Inactive
1 : Active
--
0
PTC Thermistor Input
0 :
1 :
2 :
3 :
(Hz setting)
x
RS-485
x
RS-485
(OPR command)
x
x
RS-485
RS-485
: Enable by inverter
and RS-485
RS-485 : Enable by RS-485
x : Enable by inverter
--
0
Serial Link
(Frequency)
0.1 Hz 0.0
0.0: cancel 0.1 to 400.0Hz
Non-linear V/f Pattern
(Voltage)
1 V 460230
0 to 240V : AVR active (230V class) 0 to 500V : AVR active (460V class)
0.00 to 3600s
0.01 s 6.00
ACC/DEC Time (Jogging operation)
0.0 (Depends on F16 : Freq. limiter (Low))
0.1 to 60.0Hz
0.1 Hz 2.0
Bottom Limiter (Min. freq. when
limiter is activated)
Adjustment is needed when capacitor is replaced.
-
Capacity of DC bus capacitor
--
-
Adjustment is needed when cooling fan is replaced.
Accumulated Run Time of Cooling Fan
-
h
0 : Inactive
1 : Active
--
0
Automatic Deceleration
(Frequency drop rate)
0.00 (equivalent to DEC time)
0.01 to 100.00Hz/s, 999(cancel)
0.01 Hz/s 999
Overload Prevention Control
See Note 2.
Func.
code
Name Data setting range Factory settingMin. Unit
Func.
code
Name Data setting range Factory settingMin. Unit
Func.
code
Name Data setting range Factory settingMin. Unit
--
3
STOP Key Priority / Start Check
Function
See Note 2.
--
3
Protection/Maintenance Function
Returns to zero after data clear by H97 setting at 1.
--
0
Clear Alarm Data
0.00 to 0.20
Gain for Suppression of Output Current Fluctuation
0.01
-
0.20
(Remote process command)
P (Gain)
I (Integration time)
D (Differentiation time)
(Feedback filter)
0 : Inactive 1 : Process control use (Normal action)
2 : Process control use (Inverse action)
0 : Keypad 1 : PID process command 1 4 : Communication
--
0
--
0
0.000 to 10.000 times
0.001 Times
0.100
0.0 to 3600.0s
0.1 s 0.0
0.00 to 600.00s 0.01 s 0.00
0.0 to 900.0s
0.1 s 0.5
PID Control
Application Functions: J Codes
(Timer)
(Baud rate)
(Data length)
(Parity check)
(Stop bits)
(No response error detection time)
(Response interval)
Link Functions: y Codes
0 : 2400bps 1 : 4800 2 : 9600 3 : 19200
0 : 8 bit 1 : 7 bit
0.0 to 60.0s
(Mode selection
on no response error)
0 : Trip and alarm 1 : Operation for y03 timer, alarm
2 : Operation for y03 timer, and retry to communicate.
If retry fails, the inverter trips
3 : Continuous operation
--
0
0.1 s 2.0
--
3
--
0
0 : No checking 1 : Even parity 2 : Odd parity
--
0
0 : 2 bits 1 : 1 bit
--
0
0 : No detection 1 : 1 to 60s 1 s 0
0.00 to 1.00s
0.01 s 0.01
(Protocol selection)
0 : Modbus RTU protocol 1 : SX protocol (Loader protocol)
2 : Fuji general-purpose inverter protocol
--
0
(Station address)
1 to 255
1
-
1
RS485 Communication
(Freq. setting) (OPR command)
0 : by H30 by H30
1 : from RS-485 by H30
2 : by H30 from RS-485
3 : from RS-485 from RS-485
--
0
Link Function for Supporting
Data Input
(Monitor)
Note 1: The above setting ranges may be limited by the signs or the number of digits.
Note 2: Do not change the settings in and ,as inverter does not use them although they are displayed.
<Changing, reflecting or storing data during operation>
: Disable : Change with keys and then save or reflect with key. : Change or reflect with keys and then save with key.
*) This function is OFF for single-phase series regardless of the settings.
23