Function Settings
Function Settings
Extension Terminal Functions: E codes
Selects from the following functions by code.
0 : No function selection 2 : Aux. freq. setting 2
1 : Aux. freq. setting 1 3 : PID process command 1
--
0
Built-in Potentiometer
(Function selection)
Selects from the following functions by code.
0 : No function selection 3 : PID process command 1
1 : Aux. freq. setting 1 5 : PID feedback value
2 : Aux. freq. setting 2
0 : Keypad operation ( or key)
1 : Analog voltage input (terminal 12) (0 to +10V DC)
2 : Analog current input (terminal C1) (+4 to +20mA DC)
3 :
Analog voltage input (terminals 12) and analog current input (terminal C1)
4 : Potentiometer on the keypad
--
0
--
0
Analog Input Signal Definition for: [12]
[C1]
Selects from the following items by code.
0 : (1000) Multistep freq. selection (0 to 1 step)
1 : (1001) Multistep freq. selection (0 to 3 step)
2 : (1002) Multistep freq. selection (0 to 7 step)
4 : (1004) ACC/DEC time selection (2 steps)
6 : (1006) 3-wire operation stop command
7 : (1007) Coast-to-stop command
8 : (1008) Alarm reset
9 : (1009) Trip command (External fault)
10 : (1010) Jogging operation
11 : (1011) Freq. set 2 / Freq. set 1
19 : (1019) Write enable for keypad (Data changeable)
20 : (1020) PID control cancel
21 : (1021) Normal/Inverse mode changeover
24 : (1024) Link enable (RS-485 (standard), BUS (option))
33 : (1033) PID integration/differentiation reset
34 : (1034) PID integration hold
98 : Forward operation command
99 : Reverse operation command
*
The number in ( ) indicates logical inverse. (OFF when short-circuited)
--
98
--
99
Terminal Command Assignment to: [FWD]
[REV]
[SS1]
[SS2]
[SS4]
[RT1]
[HLD]
[BX]
[RST]
[THR]
[JOG]
[Hz2/Hz1]
[WE-KP]
[Hz/PID]
[IVS]
[LE]
[PID-RST]
[PID-HLD]
[FWD]
[REV]
0.00 to 100.00%
0.01 % 0.00
0.00 to 200.00%
0.01 % 100.0
0.00 to 5.00s
0.01 s 0.05
0.00 to 100.00%
0.01 % 100.0
Analog Input Adjustment
(Gain for terminal input [12])
(Gain)
(Filter)
(Gain reference point)
Analog Input Adjustment
(Gain for terminal input [C1])
(Gain)
(Filter)
(Gain reference point)
Bias(Frequency command 1)
(Bias reference point)
Bias (PID command 1) (Bias value)
(Bias reference point)
-100.00 to 100.00%
0.01 % 0.00
0.00 to 100.00%
0.01 % 0.00
0.00 to 200.00%
0.01 % 100.0
0.00 to 5.00s
0.01 s 0.05
0.00 to 100.00%
0.01 % 100.0
Motor Parameters: P codes
0.1 % 0.0
1
0.01 to 10.00 HP (when = 1)
0.01 to 10.00 kW (when = 0, 3, or 4)
0.00 to 99.99A
0.0 to 200.0%
0.01 HP
0.01 kW
0.01 A
Nominal applied
motor capacity
Rated current of Fuji's
standard motor
Motor Parameters
(Rated capacity)
(Rated current)
(Slip compensation gain)
0 : Standard motor (R123, R90)
1 : U.S.-made motor
3 : Standard motor (R88, R90)
4 : Others
--
Motor Selection
--
2
Control Functions of Frequency: C codes
Jump Frequency Band
0.0 to 30.0Hz 0.1 Hz 3.0
0.0 to 400.0Hz
0.1 Hz 0.0
0.0
0.0
Jump Frequency 1
2
3
Multi-step Frequency Settings 1
2
3
4
5
6
7
0.00 to 400.00Hz
0.01 Hz 0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00 to 400.00Hz
0.01 Hz 0.00
Jogging Frequency
0 : Inactive 1 : Active
--
0
Timer Operation
Frequency Command 2
Func.
code
Name Data setting range Factory settingMin. Unit
Func.
code
Name Data setting range Factory settingMin. Unit
Func.
code
Name Data setting range Factory settingMin. Unit
22