Chapter 6: Function codes and application example
28
C codes: Control functions of frequency
Code Name Data setting range Default setting
C01 1 0.0
C02 2 0.0
C03 3
0.0 to 400.0 Hz
0.0
C04
Jump frequency
Hysteresis width 0.0 to 30.0 Hz 3.0
C05 1 0.00
C06 2 0.00
C07 3 0.00
C08 4 0.00
C09 5 0.00
C10 6 0.00
C11 7 0.00
C12 8 0.00
C13 9 0.00
C14 10 0.00
C15 11 0.00
C16 12 0.00
C17 13 0.00
C18 14 0.00
C19
Multistep frequency
15
0.00 to 400.00 Hz
0.00
C20 Jogging Frequency 0.00 to 400.00 Hz 0.00
C21 Timer Operation Mode Selection 0 : Disable
1 : Enable
0
C30 Frequency command 2 0 : Enable arrow keys on the keypad
1 : Enable voltage input to terminal [12] (-10 to 10V DC)
2 : Enable current input to terminal [C1] (4 to 20 mA)
3 : The sum of voltage and current inputs terminals [12] and [C1]
5 : Enable voltage input to terminal [V2] (0 to 10V DC)
7 : Enable terminal command (UP) / (DOWN) control
11 : DI interface card (option)
12 : PG / SY interface card (option)
2
C31 Offset -5.0 to 5.0 % 0.0
C32 Gain
0.00 to 200.00 % 100.0 %
C33 Filter time constant 0.00 to 5.00 s 0.05
C34 Gain base point 0.00 to 100.00 % 100.0 %
C35
Analogue input adjustment for [12]
Polarity 0 : Bipolar
1 : Unipolar
1
C36 Offset -5.0 to 5.0 % 0.0
C37 Gain
0.00 to 200.00 % 100.0
C38 Filter time constant 0.00 to 5.00 s 0.05
C39
Analogue input adjustment for [C1]
Gain base point 0.00 to 100.00 % 100.0
C41 Offset -5.0 to 5.0 % 0.0
C42 Gain 0.00 to 200.00 % 100.0
C43 Filter time constant 0.00 to 5.00 s 0.05
C44
Analogue input adjustment for [V2]
Gain base point 0.00 to 100.00 % 100.0
C50 Bias base point (Frequency command 1)
Bias base point
0.00 to 100.00 %
0.00
C51 Bias value -100.00 to 100.00 % 0.00
C52
Bias for PID command
Bias reference point 0.00 to 100.00 % 0.00
C53 Selection of normal/inverse operation
(Frequency command 1)
0: Normal operation
1: Inverse operation
0

Other manuals for Fuji Electric FRENIC-Multi